| 2015-12-14 08:47:36 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC 2014 RESIDENTIAL, CITY OF WEST PALM BEACH MUNICIPAL |
| | CODE 94-546(B), FBC 107, FBC 110.7, FBC 104.1, THIS |
| | IMPROVEMENT APPEARS TO BE LOCATED IN THE SPECIAL HAZARD |
| | FLOOD AREA. PROVIDE THE FOLLOWING INFORMATION: |
| | |
| | 1. SURVEY OF THE PROPERTY INCLUDING ELEVATIONS |
| | (TOPOGRAPHIC INFORMATION). THE SURVEY IS TO INCLUDE THE |
| | FOLLOWING: |
| | |
| | NORTH ORIENTATION |
| | PARCEL BOUNDARIES AND LOCATION AND NAMES OF ADJACENT |
| | STREETS |
| | FLOOD BOUNDARIES THAT RUN THROUGH THE PARCEL IF |
| | APPLICABLE |
| | ALL DRAINAGE AND UTILITY EASEMENTS |
| | ALL AREAS TO BE CLEARED, CUT, GRADED, OR FILLED |
| | THE LOCATION OF ALL EXISTING AND PROPOSED FENCES, |
| | WALLS, AND OTHER STRUCTURES |
| | FOOTPRINT OF ALL EXISTING AND PROPOSED BUILDINGS |
| | THE ELEVATION OF THE LOWEST FLOOR OF THE BUILDING AND |
| | OF THE ATTACHED GARAGE |
| | THE LOCATION AND ELEVATION OF ALL MECHANICAL AND |
| | UTILITY EQUIPMENT SERVICING THE BUILDING |
| | |
| | 2. SHEET S1 AND OTHER PAGES, REVISE PLANS TO CLARIFY |
| | PROPOSED DESIGN FLOOR ELEVATION OF FINISHED FLOOR FOR |
| | THE RESIDENCE. |
| | |
| | 3. SHEET S1 AND OTHER PAGES, REVISE PLANS TO CLARIFY |
| | PROPOSED DESIGN FLOOR ELEVATION FOR THE GARAGE. THE |
| | GARAGE FINISHED FLOOR ELEVATION IS TO BE A MINIMUM OF |
| | 7'6" OR IS TO INCLUDE ENOUGH FLOOD VENTS TO COMPLY WITH |
| | THE REQUIREMENTS OF NFIP TECHNICAL BULLETIN #1 |
| | (OPENINGS IN FOUNDATION WALLS AND WALLS OF |
| | ENCLOSURES"). IF FLOOD VENTS ARE PROPOSED, REVISE PLAN |
| | TO SHOW SIZE AND LOCATION. IF ENGINEERED FLOOD VENTS |
| | ARE PROPOSED, PROVIDE ENGINEERING OR PRODUCT APPROVAL. |
| | |
| | 4. SHEETS S1 AND OTHER PAGES, REVISE PLANS TO INCLUDE |
| | PROPOSED ELEVATION AND LOCATION OF EQUIPMENT SERVICING |
| | THE BUILDING. |
| | |
| | 5. A "CONSTRUCTION DOCUMENT" ELEVATION CERTIFICATE IS |
| | RECOMMENDED AT THIS TIME TO AVOID INSPECTION AND C.O. |
| | DELAYS. THIS DOCUMENT WILL BE REVIEWED AND ANY ISSUES |
| | WILL BE REQUIRED TO BE CORRECTED PRIOR TO C.O. BUT WILL |
| | NOT DELAY ISSUANCE OF THIS PERMIT. |
| | |
| | 6. ADVISORY ONLY, A "BUILDING UNDER CONSTRUCTION" |
| | ELEVATION CERTIFICATE IS RECOMMENDED AT TIME OF FORM |
| | BOARD INSPECTION. A FORM BOARD SURVEY WILL BE REQUIRED. |
| | |
| | 7. ADVISORY ONLY, A "FINISHED CONSTRUCTION" ELEVATION |
| | CERTIFICATE WILL BE REQUIRED AFTER THE FINAL FINISHED |
| | GRADE, BEFORE FINAL INSPECTION/CERTIFICATE OF OCCUPANCY |
| | (C.O.). |
| | |
| | |
| | |
| | |
| | |
| | |
| | B. THE FINISHED FLOOR DFE IS TO BE A MINIMUM OF 6" |
| | ABOVE BFE. REVISE PLAN TO SHOW PROPOSED FINISHED FLOOR |
| | ELEVATION. |
| | |
| | C. |