| Plan Review Notes For Permit 15120320 |
| Permit Number |
15120320 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-13 14:59:49 | 1ST REVIEW: FBC 2014 RESIDENTIAL MECHANICAL | | | | | | 1) THE MANUAL J WORKSHEETS SHOW HIGHER U-VALUES FOR THE | | | WINDOWS THAT DON'T MATCH THE U-VALUES SHOWN ON THE | | | ENERGY CALCULATION FORM R405-2014. PLEASE CORRECT. | | | 2) THERE IS NO DATA LISTED ON THE MANUAL J WORKSHEETS | | | FOR THE EXTERIOR DOORS AT THE FOYER AND AT GUEST BATH, | | | AND THE ENERGY FORM DOES NOT LIST ANY DATA FOR THE | | | FRONT ENTRY DOORS, AND REAR DOOR AT THE GUEST BATH. | | | 3) REFER TO SECTION M1305.1.1 FBC-14 RESIDENTIAL AND | | | INDICATE COMPLIANCE FOR THE SIZE OF THE AC CLOSETS: THE | | | WIDTH OF THE ENCLOSING SPACES AT LEAST 12 INCHES WIDER | | | THAN THE AIR HANDLERS. | | | 4) REFER TO SECTION R322.1.6 AND SHOW THE LOCATIONS OF | | | THE AC CONDENSERS ON THE PLANS, AND THE ELEVATION | | | HEIGHT OF THE MOUNTING PADS. PLEASE ALSO PROVIDE | | | DETAILS FOR CONSTRUCTION OF THE PADS. | | | 5) CORRECT THE 2010 FBC REFERENCE SHOWN IN THE ACCU | | | DETAIL ON SHEET 1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|