Plan Review Notes
Plan Review Notes For Permit 15120320
Permit Number 15120320
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-11 17:02:121ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 1- POOL ON A SEPERATE PERMIT
 2- PROVIDE GFCI PROTECTION ON KITCHEN COUNTERTOP ,
 GARAGE DOOR, FRONT AND BACK OF RESIDENCE. NEC 210.8 A /
 NEC 210.52 E
 3- 210.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 (A) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND
 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED
 IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION
 ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS
 SHALL
 BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
 COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF
 THE
 BRANCH CIRCUIT. ( MAKE SURE AFCI PROTECTION IS ON ALL
 THESE AREAS. )
 4-NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
 5- NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT. ( SHOW AC UNITS ON FLOOR
 PLAN.)
 6-FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
 7- FBC-ER 404.1.1 / 402.4.4
 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT
 AS WELL AS IC RATED AND SEALED TO NOT COMPROMISE
 BUILDING THERMAL ENVELOPE. ( 2 CFM )
  
  