| 2015-12-10 06:11:06 | 1) I AM QUESTIONING THE VALUE OF $2000.00 FOR THIS |
| | PROJECT.WPB AMEND. TO FBC SEC. 109.3. THE APPLICANT |
| | SHALL SHOW DETAILED, QUANTITY ESIMATES,AND/OR BONA FIDE |
| | CONTRACTS FOR APPROVAL. |
| | 2) SHOW THE DIMENSIONS OF THE SHOWER AND ALL FIXTURE |
| | CLEARANCES ON THE PLAN FOR THE PLUMBING FIXTURES. |
| | COMPLY WITH 2014 FBC SEC.P2705.THE SHOWER SHALL BE A |
| | MIN. OF 30 INCHES WIDE AND A TOTAL OF 900 SQ. INCHES. |
| | 3) THE SEWER HAS ALSO BEEN REPLACED AT THIS ADDRESS. |
| | THIS WORK SHALL BE INCLUDED IN THE DESCRIPTION OF THE |
| | WORK AND ALSO IN THE VALUATION.WPB AMEND. TO FBC |
| | SEC.107.2.1. |
| | 4) SUBMIT TWO COPIES OF A SURVEY SHOWING THE SIZE AND |
| | LOCATION OF THE SEWER LINE THAT WAS REPLACED. |
| | 5) SOME OF THE FOOTING FOR THE STRUCTURE HAS BEEN |
| | CHIPPED AWAY TO MAKE ROOM FOR THE NEW DRAIN COMING FROM |
| | THE REMODELED BATHROOM.SUBMIT A REPAIR DETAIL FOR THE |
| | FOOTING REPAIR SIGNED AND SEALED BY AN ENGINEER |
| | REGISTERED IN THE STATE OF FLORIDA AND ALSO A SEPARATE |
| | SIGNED AND SEALED LETTER THAT SPECIFICALLY ADDRESSES |
| | THE STRUCTURAL INTEGRITY OF THE FOOTING . WPB AMEND. TO |
| | FBC SEC. 107.1, FBCR301.1. |
| | 6) ALL UNPERMITTED WORK SHALL BE UNCOVERED FOR |
| | INSPECTION INCLUDING THE NEW SEWER.WPB AMEND. TO FBC |
| | SEC.110.1. |
| | 7) THERE WAS NEW INTERIOR FRAMING DONE IN THE REMODELED |
| | BATHROOM. SUBMIT A SET OF PLANS THAT CLEARLY REFLECTS |
| | ALL THE UNPERMITTED WORK THAT WAS DONE AND IS TO BE |
| | PERMITTED ALONG WITH ALL OTHER WORK TO BE DONE, THE |
| | SUBMITTED PLANS ARE DEFICIENT AS TO THE SCOPE OF WORK |
| | THAT I OBSERVED ONSITE. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |