Plan Review Notes
Plan Review Notes For Permit 15120307
Permit Number 15120307
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-10 06:11:061) I AM QUESTIONING THE VALUE OF $2000.00 FOR THIS
 PROJECT.WPB AMEND. TO FBC SEC. 109.3. THE APPLICANT
 SHALL SHOW DETAILED, QUANTITY ESIMATES,AND/OR BONA FIDE
 CONTRACTS FOR APPROVAL.
 2) SHOW THE DIMENSIONS OF THE SHOWER AND ALL FIXTURE
 CLEARANCES ON THE PLAN FOR THE PLUMBING FIXTURES.
 COMPLY WITH 2014 FBC SEC.P2705.THE SHOWER SHALL BE A
 MIN. OF 30 INCHES WIDE AND A TOTAL OF 900 SQ. INCHES.
 3) THE SEWER HAS ALSO BEEN REPLACED AT THIS ADDRESS.
 THIS WORK SHALL BE INCLUDED IN THE DESCRIPTION OF THE
 WORK AND ALSO IN THE VALUATION.WPB AMEND. TO FBC
 SEC.107.2.1.
 4) SUBMIT TWO COPIES OF A SURVEY SHOWING THE SIZE AND
 LOCATION OF THE SEWER LINE THAT WAS REPLACED.
 5) SOME OF THE FOOTING FOR THE STRUCTURE HAS BEEN
 CHIPPED AWAY TO MAKE ROOM FOR THE NEW DRAIN COMING FROM
 THE REMODELED BATHROOM.SUBMIT A REPAIR DETAIL FOR THE
 FOOTING REPAIR SIGNED AND SEALED BY AN ENGINEER
 REGISTERED IN THE STATE OF FLORIDA AND ALSO A SEPARATE
 SIGNED AND SEALED LETTER THAT SPECIFICALLY ADDRESSES
 THE STRUCTURAL INTEGRITY OF THE FOOTING . WPB AMEND. TO
 FBC SEC. 107.1, FBCR301.1.
 6) ALL UNPERMITTED WORK SHALL BE UNCOVERED FOR
 INSPECTION INCLUDING THE NEW SEWER.WPB AMEND. TO FBC
 SEC.110.1.
 7) THERE WAS NEW INTERIOR FRAMING DONE IN THE REMODELED
 BATHROOM. SUBMIT A SET OF PLANS THAT CLEARLY REFLECTS
 ALL THE UNPERMITTED WORK THAT WAS DONE AND IS TO BE
 PERMITTED ALONG WITH ALL OTHER WORK TO BE DONE, THE
 SUBMITTED PLANS ARE DEFICIENT AS TO THE SCOPE OF WORK
 THAT I OBSERVED ONSITE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  