| 2015-12-08 19:06:39 | RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- ACCORDING TO SEC. 1609.4 OF FBC-BUILDING, 5TH |
| | EDITION THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT |
| | "C". ENGINEER DOING THE RAS 117 CALCULATIONS TO REVISE |
| | CALCULATIONS AS REQUIRED.. NOTE: NEED TO SELECT ANOTHER |
| | FLAT ROOF ASSEMBLY THAT MEETS THE CALCULATED REVISED |
| | DESIGN PRESSURES. |
| | |
| | 2- THE BUILDING HEIGHT OF THIS BUILDING IS 110'. |
| | PROVIDE SIGNED AND SEALED DETAILS AND SPECIFICATIONS |
| | FOR THE ATTACHMENT OF THE COPING CAPS AND DRIP EDGE |
| | SHOWING COMPLIANCE WITH THE WIND LOADS OF SEC. 1609 OF |
| | FBC-BUILDING, 5TH EDITION. |
| | |
| | 3- SCOPE OF WORK SUBMITTED INCLUDES MECHANICAL UNITS |
| | STANDS, MECHANICAL SHROUDS, CONSTRUCTION OF KNEE WALL, |
| | REPLACE DOOR. THIS SCOPE OF WORK TO BE DONE UNDER |
| | SEPARATE PERMITS. PROVIDE COMPLETE DETAILS/ |
| | SPECIFICATIONS AND PRODUCT APPROVALS UNDER SEPARATE |
| | PERMITS. NOTE: THIS SCOPE OF WORK CAN NOT BE DONE BY |
| | THE ROOFING CONTRACTOR UNLESS THE ROOFING CONTRACTOR |
| | POSSES A LICENSE TO PERFORM SUCH SCOPE OF WORK. SEC. |
| | 489.113 FLORIDA STATUTES. |
| | |