Plan Review Notes
Plan Review Notes For Permit 15120279
Permit Number 15120279
Review Stop M
Sequence Number 1
Notes
Date Text
2015-12-15 17:30:321ST REVIEW 2014 MECHANICAL
 PERMIT #15120279
 12/15/15
  
 1) PROVIDE THE SEQUENCE OF OPERATION FOR THE NEW
 KITCHEN EXHAUST FAN. WILL IT BE MAUTO OR MANUALLY
 CONTROLLED?
 2) INDICATE HOW MAKE-UP AIR WILL BE PROVIDED TO THE NEW
 KITCHEN EXHAUST FAN.
 3) THE OUTDOOR AIR CALCULATIONS ARE NOT IN COMPLIANCE
 WITH TABLE 403.3: DINING ROOMS REQUIRE 7.5 CFM PER
 PERSON AND 0.18 CFM PER SQ.FT. PLEASE CORRECT AND
 PROVIDE AN AIR BALANCE CALCULATION.
 4) PROVIDE AN INSTALLATION DETAIL FOR THE RELOCATED
 HEAT PUMP, AND PROVIDE DETAILS FOR CONDENSATE DISPOSAL.
 5) PROVIDE A MIAMI-DADE NOA FOR THE EXHAUST LOUVER.
 6) REFER TO SECTION 501.3.1 AND PROVIDE CLEARANCE
 DISTANCE MEASUREMENTS FOR THE NEW KITCHEN EXHAUST
 TERMINATION.
 7) SUBMIT MANUFACTURER'S CUT SHEETS FOR THE NEW OVENS
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. PLEASE
 NOTE GREASE OR HEAT HOODS FOR EXHAUST MAY BE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved