| 2015-12-10 15:15:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. SHEET 1.1 - AN INCORRECT REFERENCE TO THE FIRE CODE |
| | IS INDICATED. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | A RE-REVIEW OF THE DESIGN MAY BE NECESSARY TO ENSURE |
| | COMPLIANCE WITH THE NEWER EDITION OF THE CODE. |
| | |
| | 2. SHEET 3.1 - TWO OVENS ARE INDICATED. NO REFERENCE IS |
| | INDICATED AS TO THE TYPE OF COOKING IS INDICATED. ALL |
| | COOKING EQUIPMENT SHALL COMPLY WITH NFPA 1 CHAPTER 50 |
| | AND NFPA 96. |
| | |
| | 3. SHEET 3.1 - THE PROPOSED PLAN INDICATES ONE EXIT |
| | FROM THE OCCUPANCY. PLEASE PROVIDED JUSTIFICATION IN |
| | COMPLICANCE WITH NFPA 101, CHAPTER 36, 36.2.4.3 AND |
| | 36.2.4.4 OR PROVIDE A SECOND EXIT TO THE OCCUPANCY. THE |
| | ENTIRE BUILDING OCCUPANCY IS NOT A MALL OR 2ND FLLOR |
| | CORRIDOR IS NOT MALL PEDESTRIAN WAY. |
| | |
| | 4. SHEET 3.1 - THE PROPOSED PLAN INDICATES A NEW 1-HOUR |
| | WALL AT THE REAR OF THE KITCHEN AREA. THIS CREATES A |
| | NEW SPACE/CORRIDOR. PLEASE PROVIDE A STATEMENT |
| | INDICATED THAT THIS SHALL SHALL ALSO COMPLY WITH ALL |
| | APPROPRIATE CODE AND STANDARDS, INCLUDING, BUT NOT |
| | LIMITED TO, FIRE SPRINKLERS, EXIT AND EMERGECNY |
| | LIGHTING, EXIT DOOR HARDWARE, ETC. |
| | |
| | 5. ADDITIONAL COMMNETS MAY BE GENERATED ON RE-SUBMITTAL |
| | OF THE ABOVE. |
| | |
| | PETER LEDUC |