| Plan Review Notes For Permit 15120279 |
| Permit Number |
15120279 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-06 13:31:16 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | | | | 1- SITE CURRENT CODE STANDARDS NEC 2011 , FBC 2014 | | | 2- NEC 210.8 B2 COMMERCIAL KITCHENS AND SINKS GFCI | | | PROTECTED 15/20 AMP OUTLETS. | | | 3- EXIT LIGHT REQUIRED IN KITCHEN AREA NEC 700.16 | | | EMERGENCY ILLUMINATION. | | | 4- ILLUMINATION. ILLUMINATION SHALL BE PROVIDED FOR ALL | | | WORKING SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS, | | | PANELBOARDS, OR MOTOR CONTROL CENTERS INSTALLED INDOORS | | | AND | | | SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. NEC | | | 110.26 D | | | 5- PLEASE MAKE NOTE OF FBC E SECTION C 405 LIGHTING | | | CONTROLS | | | 6- PLEASE SHOW LUMINAIRE DISCONNECTING MEANS 430.130 G | | | AND LUMINAIRE | | | SUPPORT NEC 410.36 B | | | 7- DOESN'T SHOW LIGHTING IN 277/480 PANEL H REFERENCE | | | FIXTURE SCHEDULE. | | | |
|