2016-01-06 13:31:161ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 1- SITE CURRENT CODE STANDARDS NEC 2011 , FBC 2014
 2- NEC 210.8 B2 COMMERCIAL KITCHENS AND SINKS GFCI
 PROTECTED 15/20 AMP OUTLETS.
 3- EXIT LIGHT REQUIRED IN KITCHEN AREA NEC 700.16
 EMERGENCY ILLUMINATION.
 4- ILLUMINATION. ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS,
 PANELBOARDS, OR MOTOR CONTROL CENTERS INSTALLED INDOORS
 AND
 SHALL NOT BE CONTROLLED BY AUTOMATIC MEANS ONLY. NEC
 110.26 D
 5- PLEASE MAKE NOTE OF FBC E SECTION C 405 LIGHTING
 CONTROLS
 6- PLEASE SHOW LUMINAIRE DISCONNECTING MEANS 430.130 G
 AND LUMINAIRE
 SUPPORT NEC 410.36 B
 7- DOESN'T SHOW LIGHTING IN 277/480 PANEL H REFERENCE
 FIXTURE SCHEDULE.
  