2015-12-16 13:09:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120279
 ADD: 515 N FLAGLER DR SUITE # 201
 CONT: CUTTING EDGE BUILDING SYSTEMS
 TEL: 561-625-4545
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. DEC. 16/ 2015
 ACTION: DENIED
  
 1) THE COVER SHEET 1.1 INDICATES THE PLANS WERE
 DESIGNED TO THE 2010 FBC FAMILY OF CODES. THE FIFTH
 EDITION OF THE 2014 FBC (2014 ED.) WAS ADOPTED STATWIDE
 ON JUNE 30/ 2015. PLEASE UPDATE THE PLANS TO THE
 CURRENT CODE.
  
 2) SHEET 3.1 THE FLOOR PLAN INDICATES THE USE OF TPG
 FIREGLASS 20 AND METAL FRAME. PLEASE PROVIDE COMPLIANCE
 WITH:
  
 2A) FBC-B 716.2 FIRE-RESISTANCE-RATED GLAZING.
 FIRE-RESISTANCE-RATED GLAZING TESTED AS PART OF A
 FIRE-RESISTANCE-RATED WALL ASSEMBLY IN ACCORDANCE WITH
 ASTM E 119 OR UL 263 AND LABELED IN ACCORDANCE WITH
 SECTION 703.6 SHALL BE PERMITTED IN FIRE DOORS AND FIRE
 WINDOW ASSEMBLIES WHERE TESTED AND INSTALLED IN
 ACCORDANCE WITH THEIR LISTINGS AND SHALL NOT OTHERWISE
 BE REQUIRED TO COMPLY WITH THIS SECTION.
  
 2B) FBC-B 716.3 MARKING FIRE-RATED GLAZING ASSEMBLIES.
 FIRE-RATED GLAZING ASSEMBLIES SHALL BE MARKED IN
 ACCORDANCE WITH TABLES 716.3, 716.5, AND 716.6.
  
 2C) FBC-B 716.3.1 FIRE-RATED GLAZING THAT EXCEEDS THE
 CODE REQUIREMENTS. FIRE-RATED GLAZING ASSEMBLIES MARKED
 AS COMPLYING WITH HOSE STREAM REQUIREMENTS (H) SHALL BE
 PERMITTED IN APPLICATIONS THAT DO NOT REQUIRE
 COMPLIANCE WITH HOSE STREAM REQUIREMENTS. FIRE-RATED
 GLAZING ASSEMBLIES MARKED AS COMPLYING WITH TEMPERATURE
 RISE REQUIREMENTS (T) SHALL BE PERMITTED IN
 APPLICATIONS THAT DO NOT REQUIRE COMPLIANCE WITH
 TEMPERATURE RISE REQUIREMENTS. FIRE-RATED GLAZING
 ASSEMBLIES MARKED WITH RATINGS (XXX) THAT EXCEED THE
 RATINGS REQUIRED BY THIS CODE SHALL BE PERMITTED.
  
 2D) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
  
 2E) PLEASE SHOW COMPLIANCE WITH: 2014 FBC-ACCESSIBILITY
 CODE 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  