| 2015-12-16 13:09:37 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120279 |
| | ADD: 515 N FLAGLER DR SUITE # 201 |
| | CONT: CUTTING EDGE BUILDING SYSTEMS |
| | TEL: 561-625-4545 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 16/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE COVER SHEET 1.1 INDICATES THE PLANS WERE |
| | DESIGNED TO THE 2010 FBC FAMILY OF CODES. THE FIFTH |
| | EDITION OF THE 2014 FBC (2014 ED.) WAS ADOPTED STATWIDE |
| | ON JUNE 30/ 2015. PLEASE UPDATE THE PLANS TO THE |
| | CURRENT CODE. |
| | |
| | 2) SHEET 3.1 THE FLOOR PLAN INDICATES THE USE OF TPG |
| | FIREGLASS 20 AND METAL FRAME. PLEASE PROVIDE COMPLIANCE |
| | WITH: |
| | |
| | 2A) FBC-B 716.2 FIRE-RESISTANCE-RATED GLAZING. |
| | FIRE-RESISTANCE-RATED GLAZING TESTED AS PART OF A |
| | FIRE-RESISTANCE-RATED WALL ASSEMBLY IN ACCORDANCE WITH |
| | ASTM E 119 OR UL 263 AND LABELED IN ACCORDANCE WITH |
| | SECTION 703.6 SHALL BE PERMITTED IN FIRE DOORS AND FIRE |
| | WINDOW ASSEMBLIES WHERE TESTED AND INSTALLED IN |
| | ACCORDANCE WITH THEIR LISTINGS AND SHALL NOT OTHERWISE |
| | BE REQUIRED TO COMPLY WITH THIS SECTION. |
| | |
| | 2B) FBC-B 716.3 MARKING FIRE-RATED GLAZING ASSEMBLIES. |
| | FIRE-RATED GLAZING ASSEMBLIES SHALL BE MARKED IN |
| | ACCORDANCE WITH TABLES 716.3, 716.5, AND 716.6. |
| | |
| | 2C) FBC-B 716.3.1 FIRE-RATED GLAZING THAT EXCEEDS THE |
| | CODE REQUIREMENTS. FIRE-RATED GLAZING ASSEMBLIES MARKED |
| | AS COMPLYING WITH HOSE STREAM REQUIREMENTS (H) SHALL BE |
| | PERMITTED IN APPLICATIONS THAT DO NOT REQUIRE |
| | COMPLIANCE WITH HOSE STREAM REQUIREMENTS. FIRE-RATED |
| | GLAZING ASSEMBLIES MARKED AS COMPLYING WITH TEMPERATURE |
| | RISE REQUIREMENTS (T) SHALL BE PERMITTED IN |
| | APPLICATIONS THAT DO NOT REQUIRE COMPLIANCE WITH |
| | TEMPERATURE RISE REQUIREMENTS. FIRE-RATED GLAZING |
| | ASSEMBLIES MARKED WITH RATINGS (XXX) THAT EXCEED THE |
| | RATINGS REQUIRED BY THIS CODE SHALL BE PERMITTED. |
| | |
| | 2D) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY |
| | CODE 226.1 GENERAL. WHERE DINING SURFACES ARE PROVIDED |
| | FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 |
| | PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION, |
| | WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN |
| | EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902. |
| | |
| | 2E) PLEASE SHOW COMPLIANCE WITH: 2014 FBC-ACCESSIBILITY |
| | CODE 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK |
| | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |