Plan Review Notes
Plan Review Notes For Permit 15120263
Permit Number 15120263
Review Stop G
Sequence Number 1
Notes
Date Text
2015-12-11 05:16:321) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR REVIEW FOR THE TANKLESS WATER
 HEATER. THE WATER HEATER SHALL BE LISTED AND LABELED.
 2014 FBC-FUEL GAS SEC. 304.3.
 2) SUBMIT A GAS RISER DIAGRAM FOR CHANGES MADE TO THE
 GAS PIPING. SHOW ALL EXISTING GAS APPLIANCES ON THE
 DRAWING AND THE RESPECTIVE BTU LOAD FOR EACH APPLIANCE.
 A TANKLESS WATER HEATER HAS A MUCH HIGHER BTU LOAD
 VALUE THAN A TANK TYPE. THE DRAWING IS REQUIRED TO
 CONFIRM THAT THE CURRENT GAS PIPING SYTEM IS SIZED
 PROPERLY FOR THE ADDITIONAL BTU LOAD OF THE TANKLESS
 WATER HEATEER.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  