| 2015-12-07 14:44:21 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15120220 | | | 12/7/15 | | | | | | 1) THERE ARE SEVERAL NEW LINEAR RETURN GRILLS, AND SOME | | | SUPPLY DIFFUSERS THAT DO NOT HAVE CFM QUANTITIES | | | LABELED. I HAVE HIGHLIGHTED THESE LOCATIONS. PLEASE | | | REVIEW AND REVISE. | | | 2) PLEASE REVISE THE AIR DEVICE SCHEDULE ON M0.1 TO | | | INCLUDE THE THE LINEAR GRILLS. | | | 3) THE PLAN APPEARS TO INDICATE UNBALANCED AIR FLOWS AT | | | RECEPTION ROOM 100 ( 185 CFM'S SUPPLY AIR FROM AHU-4 | | | WITH 370 CFM'S RETURN AIR TO AHU-3), AND THE OPERATIONS | | | ROOM (600 CFM'S OF SUPPLY AIR FROM AHU-4 NOT BEING | | | RETURN TO THE UNIT). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|