2015-12-07 14:44:211ST REVIEW 2014 MECHANICAL
 PERMIT #15120220
 12/7/15
  
 1) THERE ARE SEVERAL NEW LINEAR RETURN GRILLS, AND SOME
 SUPPLY DIFFUSERS THAT DO NOT HAVE CFM QUANTITIES
 LABELED. I HAVE HIGHLIGHTED THESE LOCATIONS. PLEASE
 REVIEW AND REVISE.
 2) PLEASE REVISE THE AIR DEVICE SCHEDULE ON M0.1 TO
 INCLUDE THE THE LINEAR GRILLS.
 3) THE PLAN APPEARS TO INDICATE UNBALANCED AIR FLOWS AT
 RECEPTION ROOM 100 ( 185 CFM'S SUPPLY AIR FROM AHU-4
 WITH 370 CFM'S RETURN AIR TO AHU-3), AND THE OPERATIONS
 ROOM (600 CFM'S OF SUPPLY AIR FROM AHU-4 NOT BEING
 RETURN TO THE UNIT).
  