| Plan Review Notes For Permit 15120195 |
| Permit Number |
15120195 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-08 13:34:11 | 2ND REVIEW: FBC 2014 MECHANICAL | | | REVISION #15120195 | | | 2/8/16 | | | | | | 1) SHEET M4.0: NOTES 15-20 ARE MISSING AT THE ROOF CURB | | | ANCHORING DETAIL. PLEASE CLARIFY IF THERE ARE | | | STRUCTURAL DETAILS FOR THE RTU ROOF OPENINGS- THERE ARE | | | STRUCTURAL PLANS LISTED IN THE INDEX HOWEVER NO PLANS | | | WERE INCLUDED IN THE SETS. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE ROOF | | | CURBS REVIEWED AND APPROVED BY THE EOR. | | | 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE | | | KITCHEN EXHAUST HOOD AND THE WALK-IN COOLER/FREEZER. | | | PLEASE PLACE NOTES ON THE PLAN ACCORDINGLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|