Plan Review Notes
Plan Review Notes For Permit 15120195
Permit Number 15120195
Review Stop M
Sequence Number 1
Notes
Date Text
2015-12-14 17:11:111ST REVIEW 2010 MECHANICAL
 PERMIT #15120195
 12/14/15
  
 1) PROVIDE VENTILATION CALCULATIONS IN COMPLIANCE WITH
 TABLE 403.3. FBC-10 MECHANICAL TO VERIFY COMPLIANCE OF
 THE 3200 CFM'S SHOWN IN THE AIR BALANCE SCHEDULE ON
 M1.0.
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 COMPLIANCE WITH SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION.
 3) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION 101.4.3 FBC-10 ENERGY CONSERVATION.
 4) PROVIDE AN HVA C ROOF PLAN INDICATING REQUIRED
 CLEARANCE DISTANCES FOR EXHAUST OUTLETS MECHANICAL AND
 GRAVITY AIR INTAKES.
 5) PROVIDE WIND LOAD TIE DOWN ENGINEERING AND WIND
 DESIGN CRITERIA FOR THE RTU'S, FANS, AND CURBS- REFER
 TO SECTION 301.12 FBC-10 MECHANICAL.
 6) PROVIDE DUCT HANGING AND CONNECTION DETAILS.
 7) PROVIDE THE SEQUENCE OF OPERATION FOR THE DUCT SMOKE
 DETECTORS PER SECTION 606.4, AND INDICATE IF THE TWO AC
 SYSTEMS WILL BE LINKED TOGETHER FOR FAN SHUT DOWN.
 8) INDICATE HOW THE DS DETECTORS WILL BE SUPERVISED PER
 SECTION 606.4.1
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER