| Plan Review Notes For Permit 15120195 |
| Permit Number |
15120195 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-10 06:52:36 | 1) INDICATE THE APPLICABLE PIPE SIZING TABLE ON SHT.P-5 | | | FROM THE 2010 FGC THAT WAS USED TO SIZE THE GAS | | | PIPING.FGC SEC.402.3. | | | 2) INDICATE THE TYPE OF PIPE BEING USED FOR THE GAS | | | SYSTEM. WPB AMEND.TO 2010 FBC SEC.107.2.1. | | | 3) SHT. P5.0 - KEYNOTES #16 & #17 REFER TO 2 FUTURE 1 | | | INCH GAS OUTLETS BUT THEY ARE NOT SHOWN ON THE GAS | | | RISER. CLARIFY. PROVIDE THE ESTIMATED BTU LOAD FOR THE | | | FUTURE OUTLETS. THE FUTURE OUTLETS SHALL BE EQUIPPED | | | WITH A VALVE AND A CAP. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|