Plan Review Notes
Plan Review Notes For Permit 15120195
Permit Number 15120195
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-12 08:55:22THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. YOUR FIXTURE
 SCHEDULE SHOWS RECESSED LIGHTING.
 2. FBC-B 1006.2. EMERGENCY LIGHTING IS REQUIRED. YOUR
 FIXTURE SCHEDULE IS NOT CLEAR ON THIS, REVISE
 ACCORDINGLY.
 3. NOT ALL SYMBOLS SHOWN ON THE PLANS APPEAR ON THE
 LEGEND.
 4. SUBMIT A LIGHTING DENSITY ALLOWANCE CHART IN
 COMPLIANCE WITH THE FBC-E.
 5. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 6. NEC 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A
 SHOW WINDOW FOR EVERY 12 LINEAR FT. OR MAJOR PORTION
 THEREOF AREA MEASURED HORIZONTALLY.
 7. NEC 215.5 DIAGRAMS OF FEEDERS. A RISER DIAGRAM
 SHOWING FEEDER DETAILS ALONG WITH RESPECTIVE LOAD CALCS
 SHALL BE PROVIDED. THIS DIAGRAM SHALL INCLUDE CONDUCTOR
 SIZING AND INSULATION TYPE.
 8. YOU INDICATE THAT YOUR LOAD CALCS ARE IN ACCORDANCE
 WITH NEC 220.56, BUT THEY ARE NOT. REARRANGE YOUR PANEL
 SCHEDULES TO CONFORM TO THE REQUIREMENTS OF 220.56 TO
 MAKE THE ADJUSTED DEMANDS.
 9. YOUR HOOD DETAILS REFER TO AN ELECTRICAL PAGE NOT
 INCLUDED ON THE DRAWINGS. (E3.2). PROVIDE THIS SHEET
 FOR THE SUBSEQUENT REVIEW.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER