| 2015-12-16 14:00:05 | PERMIT #15120189 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | EVENT APPROVED WITH COMMENTS: |
| | |
| | 1) TENT INSTALLATION REQUIRES A SEPERATE PERMIT. THIS |
| | PERMIT MUST BE OBTAINED NO LESS THAN 5 BUSINESS DAYS |
| | PRIOR TO THE EVENT. (IF USING A TENT COMPANY, HAVE THE |
| | TENT COMPANY APPLY FOR THE PERMIT.) |
| | |
| | 2) ALL TENTS SHALL BE OF THE OPEN AREA/NO SIDEWALL |
| | TYPE, OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT |
| | SIGNS ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE |
| | FEET. |
| | |
| | 3) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| | |
| | 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | |
| | 5) PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE |
| | CANOPY MATERIAL. |
| | |
| | 6) GENERATORS AND OTHER INTERNAL COMBUSTION POWER |
| | SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 |
| | FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| | ENCLOSURE. |
| | |
| | 7) A SITE WALK THROUGH MAY BE CONDUCTED BY A FIRE |
| | INSPECTOR, PRIOR TO THE START OF THE EVENT. |
| | |
| | |