| Plan Review Notes For Permit 15120184 |
| Permit Number |
15120184 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-10 13:33:51 | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE FIXTURE DRAIN FOR WASHING MACHINE MUST TIE INTO | | | BUILDING DRAIN DOWNSTREAM OF THE BATHROOM GROUP. PER | | | FBC P SEC 912.1 | | | SHEET P-1 REFERS TO PLUMBING CODE AS FBC 2901 IT SHALL | | | BE FBC 2014. | | | 3. P-1 AND E-1 DO NOT COMPLY WITH FAC SEC 61G15-23.003 | | | PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE | | | 4. APPLICATION REFERENCES SWIMMING POOL BUT ITS NOT ON | | | THE PRINT PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC | | | 107.2.1 | | | |
|