| Plan Review Notes For Permit 15120141 |
| Permit Number |
15120141 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-23 10:42:54 | PLAN DENIED | | | 1) SHOW LOCATION OF AIR CONDITIONING CONDENSER | | | ON MECHANICAL PLAN. PER SECTION 107 FBC 2014 | | | 2) HAVE THE SIGNATURE OF WHO EVER DREW THE PLAN | | | ON THE PLAN WITH LICENSE NUMBER. SECTION 107 | | | FBC 2014 | | | 3) PROVIDE EQUIPMENT SCHEDULE OF THE AIR CONDITIONING | | | EQUIPMENT ON MECHANICAL PLAN. PER SECTION 107 FBC 2014 | | | 4) SHOW BATHROOM EXHAUST ON MECHANICAL PLAN. | | | PER SECTION 107 2014 FBC | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|