Plan Review Notes
Plan Review Notes For Permit 15120141
Permit Number 15120141
Review Stop M
Sequence Number 2
Notes
Date Text
2016-02-23 10:42:54PLAN DENIED
 1) SHOW LOCATION OF AIR CONDITIONING CONDENSER
 ON MECHANICAL PLAN. PER SECTION 107 FBC 2014
 2) HAVE THE SIGNATURE OF WHO EVER DREW THE PLAN
 ON THE PLAN WITH LICENSE NUMBER. SECTION 107
 FBC 2014
 3) PROVIDE EQUIPMENT SCHEDULE OF THE AIR CONDITIONING
 EQUIPMENT ON MECHANICAL PLAN. PER SECTION 107 FBC 2014
 4) SHOW BATHROOM EXHAUST ON MECHANICAL PLAN.
 PER SECTION 107 2014 FBC
  