Plan Review Notes
Plan Review Notes For Permit 15120129
Permit Number 15120129
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-07 14:25:16THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. NEC 215.5, PROVIDE A SITE SPECIFIC RISER DIAGRAM
 SHOWING FEEDER DETAILS INCLUDING CONDUCTOR SIZING AND
 INSULATION TYPE.
 2. NEC 408.4(B), INDICATE THE LOCATION OF THE SOURCE OF
 POWER. IDENTIFY IF FROM THE RESIDENCE OR FROM A COMMON
 PANELBOARD AT THE DOCK.
 3. NEC 408.4(A), SHOW CIRCUIT DIRECTORY AND CLEARLY
 IDENTIFY THE RESPECTIVE CIRCUIT.
 4. INDICATE DISTANCE FROM PANEL TO MOTORS FOR VOLTAGE
 DROP CONSIDERATIONS. PER FBC-E NO MORE THAN 3% VOLTAGE
 DROP PERMITTED.
 5. A 15-20 AMP 120 VAC, GFI PROTECTED WP OUTLET
 REQUIRED WITHIN CLOSE PROXIMITY OF THE LIFT.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  