| Plan Review Notes For Permit 15120123 |
| Permit Number |
15120123 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-14 16:01:41 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | PHIL PETTY | | | 561-805-6742 | | | [email protected] | | | | | | | | | | | | TALK TO PROJECT MANAGER AND HE STATED POLARIS WILL BE | | | USED TO MAKE ATS EQUIPMENT TAPS | | | NOTE MAKE SURE TAPS DON'T EXCEED 75 % OF CUBIC INCHES. | | | | | | 312.8 SWITCH AND OVERCURRENT DEVICE ENCLOSURES WITH | | | SPLICES, TAPS, AND FEED-THROUGH CONDUCTORS. THE WIRING | | | SPACE OF ENCLOSURES FOR SWITCHES OR OVERCURRENT DEVICES | | | SHALL BE PERMITTED FOR CONDUCTORS FEEDING THROUGH, | | | SPLICED, | | | OR TAPPING OFF TO OTHER ENCLOSURES, SWITCHES, OR | | | OVERCURRENT | | | DEVICES WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE TOTAL OF ALL CONDUCTORS INSTALLED AT ANY CROSS | | | SECTION | | | OF THE WIRING SPACE DOES NOT EXCEED 40 PERCENT OF THE | | | CROSS-SECTIONAL AREA OF THAT SPACE. | | | (2) THE TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS | | | INSTALLED | | | AT ANY CROSS SECTION OF THE WIRING SPACE DOES NOT | | | EXCEED 75 PERCENT OF THE CROSS-SECTIONAL AREA OF THAT | | | SPACE. | | | (3) A WARNING LABEL IS APPLIED TO THE ENCLOSURE THAT | | | IDENTIFIES | | | THE CLOSEST DISCONNECTING MEANS FOR ANY FEEDTHROUGH | | | CONDUCTORS. |
|