| 2015-12-03 14:15:55 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. YOU SHALL MARK THE LOCATION OF ALL ELECTRICAL PANELS |
| | ON THE FLOOR PLAN. |
| | 2. NEC 210.63 A 125 V. SINGLE PHASE 15 OR 20 AMP |
| | RECEPTACLE SHALL BE INSTALLED WITHIN 25? OF THE CU?S AT |
| | AN ACCESSIBLE LOCATION TO SERVICE THE HVAC. (EACH UNIT |
| | SHALL HAVE THEIR RESPECTIVE SERVICE OUTLET POWERED FROM |
| | THE SOURCE IT SERVES.) |
| | 3. MARK THE LOCATION OF THE WASHER ON THE FLOOR PLANS. |
| | 4. NEC 210.52(E)(2) EACH GRADE LEVEL UNIT SHALL HAVE AN |
| | EXTERIOR GFCI OUTLET. |
| | 5. NEC 210.52(C)(1) IF CORNER AREA BEHIND KITCHEN SINK |
| | IS GREATER THAN 18?, AN OUTLET WILL BE REQUIRED. |
| | 6. NEC 250.94 AN INTER-SYSTEM BONDING TERMINAL SHALL BE |
| | INSTALLED AT THE SERVICE POINT FOR COMMON GROUNDING OF |
| | AUXILIARY SERVICES. |
| | 7. MARK DESIGNATED CIRCUIT INFORMATION OF FLOOR PLAN |
| | OUTLETS. |
| | 8. NEC 314.27 EVERY LUMINAIRE OUTLET INSTALLED IN THE |
| | CEILING SHALL BE LISTED TO SUPPORT 50#?S AND PADDLE FAN |
| | OUTLETS SHALL BE LISTED FOR THE APPLICATION. |
| | 9. NEC 406.12 ALL NON-LOCKING TYPE 15 & 20 AMP 125 V. |
| | RECEPTACLES IN DWELLING UNITS SHALL BE LISTED AS TAMPER |
| | RESISTANT. |
| | 10. NEC 406.9(B) ALL 15 & 20 AMP NON LOCKING TYPE |
| | RECEPTACLES INSTALLED OUTDOORS/WET LOCATIONS SHALL BE |
| | LISTED ?WR? WEATHER RESISTANT. |
| | 11. FBC-E SECTION R402.4.4 RECESSED LUMINARIES |
| | INSTALLED WITHIN THE BLDG. THERMAL ENVELOPE SHALL BE IC |
| | RATED AND SEALED TO LIMIT THE LEAKAGE OF AIR BETWEEN |
| | THE CONDITIONED AND UNCONDITIONED SPACE. |
| | 12. FBC-R SECTION R303.7 YOU SHALL PROVIDE ILLUMINATION |
| | FOR THE STAIRWAYS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |