| Notes |
| Date |
Text |
| 2015-12-07 16:57:52 | APPROVED WITH CORRECTIONS AS FOLLOWS: PER NEC 430.52 | | | THE OCPD FOR THIS FEEDER TO PROPERLY OPERATE THESE TWO | | | MOTORS IS 40 AMP. IMPORTANT NOTICE: | | | ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS | | | PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL | | | INSPECTOR. | | | NO SITE TUBES WILL BE ACCEPTED | | | |
|