Plan Review Notes
Plan Review Notes For Permit 15120092
Permit Number 15120092
Review Stop B
Sequence Number 1
Notes
Date Text
2015-12-09 06:50:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120092
 ADD: 510 43RD ST.
 CONT: CBJ CONSTRUCTION
 TEL: 305-219-9791
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. DEC. 09/ 2015
 ACTION: DENIED
  
 1) SHEET A-1 CODE CRITERIA;
  
 1A) THE PLANS INDICATE THE CODE USED IN THE DESIGN OF
 THESE DOCUMENTS WAS THE 2010 FBC. PLEASE NOTE JUNE 30/
 2015 STATEWIDE THE 5TH EDITION OF THE FAMILY OF FLORIDA
 BUILDING CODE (FBC 2014) WAS ADOPTED STATEWIDE.
  
 1B) THE WIND DESIGN CRITERIA INDICATES THIS STRUCTURE
 IS IN A WIND ZONE OF 175 MPH. PLEASE NOTE THAT UNDER
 THE 2014 FBC-B CATEGORY II BUILDINGS LIE IN A 170 MPH
 VULT WIND ZONE. SEE 2014 FBC-B FIGURE 1609A.
  
 2) SHEET A-1 BUILDING TYPE & OCCUPANCY:
 2A) THE DESIGNER OF RECORD HAS LISTED THE OCCUPANCY AS
 A R3 -SINGLE FAMILY. UNDER THE BUSINESS TAX FOR THIS
 ADDRESS IT IS LISTED FOR 10 APARTMENTS MAKING ALL
 DWELLING UNITS A R2 OCCUPANCY. 2014 FBC-B 310.4
  
 2B) IT APPEARS THERE IS A DISCREPANCY IN EITHER THE
 SCOPE OF WORK OR IN THE LEVEL OF ALTERATION THAT IS
 TAKING PLACE UNDER THIS PERMIT. SCOPE OF WORK LISTED IN
 THE PLANS MAKES IT SOUND AS THIS IS A LEVEL 1
 ALTERATION :
  
 2014 EXST. BLDG. CODE 503.1 SCOPE. LEVEL 1 ALTERATIONS
 INCLUDE THE REMOVAL AND REPLACEMENT OR THE COVERING OF
 EXISTING MATERIALS, ELEMENTS, EQUIPMENT, OR FIXTURES
 USING NEW MATERIALS, ELEMENTS, EQUIPMENT, OR FIXTURES
 THAT SERVE THE SAME PURPOSE.
  
 WHERE AS THE PLANS INDICATE A LEVEL II ALTERATION :
 504.1 SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT.
  
 WHAT PART OF THE TENANT SPACE IS BEING RECONFIGURED OR
 WHAT SYSTEM IS BEING ECONFIGURATION OR EXTENSION OF ANY
 SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT?
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  