2015-12-09 11:06:561ST REVIEW 2014 MECHANICAL
 PERMIT #15120053
 12/9/15
  
 1) SHEETS M1.1 & M5.1 : IDENTIFY ALL THE ROOMS ON THE
 PLAN WITH LABELS MATCHING THE SPACE TYPES SHOWN IN THE
 O/A CALCULATIONS SCHEDULE.
 2) M5.1: AHU-2-2 IS NOT LISTED IN O/A SCHEDULE- AHU-2-3
 IS LISTED TWICE.
 3) INDICATE THE TYPE AND SIZE OF LOUVERED DOOR FOR THE
 NEW AHU-2-2 CLOSET.
 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE RELOCATED
 AHU-2-2: SHOW THE TYPE AND SIZE OF PIPING, THE PIPING
 RUN, AND THE DISCHARGE LOCATION.
  