| 2015-12-09 09:10:54 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120053 |
| | ADD: 120 S. OLIVE AVE. SUITE? |
| | CONT: TBD |
| | TEL: 561-659-2383 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 09/2015 |
| | ACTION: DENIED |
| | |
| | 1) ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.3. THE |
| | PERMIT APPLICATION LIST THE ADDRESS OF 120 S. OLIVE |
| | AVE. NO SUITE NUMBER IS GIVEN. THE PLANS SHEET A-0.00 |
| | INDICATE THIS IS A NEW SUITES # 210, 211 & 212. SHEET |
| | A-0.00 INDICATES (EXISTING SUITES 205 & 210 BEING |
| | SUB-DIVIDED TO CREATE NEW SUITES 210, 211 & 212. THIS |
| | IS A COMMERCIAL CONDOMINIUM, WITH THE NEW SUITES BEING |
| | ADDED THE DECLARATION OF CONDOMINIUM WILL NEED TO BE |
| | UPDATED. |
| | |
| | 2) SHEET A-0.00 SOMEONE HAS X-ED OUT THE WORK SHOWN ON |
| | THE PLAN FOR THE 2ND FLOOR. THIS IS NOT BEEN INITIALED |
| | BY THE DESIGNER OF RECORD AND DATED. |
| | IN THE CODE ANALYSIS THE WRITTEN DESCRIPTION OF WORK |
| | STILL SHOWS WORK TO BE PREFORMED ON THE 6TH FLOOR. |
| | 107.2.1.3 DISCREPANCY IN PLANS, PLEASE PROVIDE |
| | ADDITIONAL INFORMATION. ONLY THE DESIGNER OF RECORD CAN |
| | MODIFY THE PLANS BY APPLYING THERE INITIALS AND DATING |
| | THE RED LINED DRAWING. FL ADMIN CODE 61G16.003 |
| | ARCHITECTS. |
| | |
| | 3A) SHEET A-0.00 SUITE # 212 THE ENTRY DOOR IT APPEARS |
| | THERE IS ONLY 12 INCHES ON THE LATCH SIDE OF THE |
| | INSWING DOOR. THE 2014 FBC-ACCESSIBILITY CODE SECTION |
| | 404.2.4 MANEUVERING CLEARANCES REQUIRES A MINIMUM OF 18 |
| | INCHES. ALSO SEE FIGURE 404.2.4.1(A). |
| | |
| | 3B) SHEET A-0.00 SUITE # 211 WHAT APPEARS TO BE A BREAK |
| | ROOM WITH REFRIGARATOR AND SINK HAS ONLY 12 INCHES ON |
| | THE LATCH SIDE OF THE INSWING DOOR. THE 2014 |
| | FBC-ACCESSIBILITY CODE SECTION 404.2.4 MANEUVERING |
| | CLEARANCES REQUIRES A MINIMUM OF 18 INCHES. ALSO SEE |
| | FIGURE 404.2.4.1(A). |
| | |
| | 3C) SHEET A-0.00 SUITE # 210 WHAT APPEARS TO BE THE |
| | RECEPTIONIST AREA THERE IS A STUB SECTION OF WALL |
| | DIRECTLY AT THE DOOR. . THE 2014 FBC-ACCESSIBILITY CODE |
| | SECTION 404.2.4 MANEUVERING CLEARANCES REQUIRES A |
| | MINIMUM OF 18 INCHES. ALSO SEE FIGURE 404.2.4.1(A). |
| | |
| | 4) NONE OF THE ARCHITECTURALS SHEETS PROVIDES |
| | IDENTIFICATION OF DOORS NOR IS THERE A DOOR SCHEDULE TO |
| | BE ABLE TO VERIFY CODE COMPLIANCE WITH: |
| | 2014 FBC-B 1008.1.1 MINIMUM EGRESS DOOR SIZE. |
| | 2014 FBC-ACCESSIBILITY 404.2.3 CLEAR WIDTH. |
| | |
| | 5) SHEET A-0.00 SUITE # 211 DOES NOT INDICATE THE |
| | USAGEIT IS NOT CLEARLY STATE IF DEPICTED IS A FLOOR |
| | SINK, WORK ROOM SINK OR A BREAK ROOM SINK IS IN THE |
| | NORTH EAST CORNER OF THE ROOM. IT IS NOT CLEAR IF |
| | COMPLIANCE WITH THE 2014 FBC-ACCESSIBILITY CODE 606. |
| | 1-5 IS REQUIRED? |
| | |
| | 6) THERE ARE NO FIRE SPRINKLER PLANS SUBMITTED SHOWING |
| | THE LOCATION OF THE EXISITNG SPRINKLER HEADS, IF HEADS |
| | NEED TO BE MOVED? THERE WERE DEMOLTION PLANS SUBMITTED |
| | SHOWING WHAT WALLS ARE OLD AND WHICH WALLS ARE MOVED |
| | AND OR NEW WALLS. 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.5.1.1 MINIMUM |
| | PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.(5) |
| | SCHEMATIC FIRE SPRINKLERS. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |