| Plan Review Notes For Permit 15120030 |
| Permit Number |
15120030 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-08 12:39:17 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRIC | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE SIZE OF THE EXISTING ELECTRICAL PANEL. | | | SUBMIT TWO COPIES OF A PANEL SCHEDULE WITH LOAD | | | CALCULATIONS TO SHOW THAT THE EXISTING PANEL IS | | | ADEQUATE FOR THE ADDITION LOADS OF THE ELECTRIC POOL | | | HEATER AND OTHER POOL EQUIPMENT. FBC 107.2.1 | | | | | | 2) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE POOL HEAT PUMP. FBC | | | 107.2.1 |
|