| 2016-02-20 03:42:42 | 1)THE PLAN SHOWS THE POOL WASTEWATER LINE DISCHARGING | | | TO THE STORM SEWER. POOL WATER IS PROHIBITED FROM | | | DISCHARGING TO THE STORM OR SANITARY SYSTEM PER CITY | | | ORDINANCE # 90-126 (B) & 90-203 (A). SPECIFY WHERE THE | | | WASTEWATER WILL DISCHARGE.3ND REQUEST. | | | 2) 2014 FBCB SEC. 454.1.5.4 REQUIRES VENTILATION IN THE | | | EQUIPMENT ROOM. SUBMIT REQUIRED VENTILATION | | | CALCULATIONS FOR REVIEW. 3ND REQUEST. THE PLAN NOTES | | | "VENTILATION BY OTHERS." I NEED TO KNOW HOW COMPLIANCE | | | WITH THIS CODE SECTION WILL BE MET. | | | 3) SUBMIT MSDS SHEETS FOR THE CHEMICALS IN THE PH TANK | | | & CHEMICAL FEEDER.WPB SEC. 107.2.1.3RD REQUEST. | | | | | | I SUGGEST SETTING AN APPOINTMENT TO REVIEW THE PLAN | | | REVIEW COMMENTS TO HELP GET THE PLUMBING APPROVED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|