| 2016-01-28 06:49:24 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120024 |
| | ADD: 312 23RD ST. |
| | CONT: ROYAL PALM POOLS |
| | TEL: 561-798-3711 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 2ND REVIEW |
| | DATE: THURS. JAN. 28/2016 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. THERE HAS BEEN NO REVISION TO THE |
| | MASTER SET OF PLANS SUBMITTED SHOWING THE POOL |
| | PLACEMENT MATCHING THE LAYOUT OF THE POOL PERMIT SET OF |
| | DRAWINGS. THERE IS A DISCREPANCY IN THE MATER BUILDING |
| | PERMIT 14120431 AND THE LAY OUT OF THE POOL PERMITTED |
| | SET OF PLANS. THE MATER BUILDING PERMIT SHOWS THE |
| | STAIRS ON THE WEST END OF THE POOL (SEE SHEETS A-2.00 & |
| | A-3.40) WHERE AS THE SUBMITTED POOL PLANS INDICATE THE |
| | STAIRS AND SHALLOW END OF THE POOL AT THE EAST END OF |
| | THE POOL. DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2) COMPLIED. SHEET 4 OF 4 POOL EQUIPMENT NOTE 11 |
| | INDICATES THERE IS TO BE A POOL GAS FIRED HEATER. SPEC |
| | SHEET SUBMITTED IS FOR MASTERTEMP HEATERS A GENERIC |
| | SPEC SHEET OF THEIR PRODUCTS. PLEASE IDENTIFY WHICH OF |
| | THEIR PRODUCTS (MODEL), GAS TYPE PROPANE OR NATURAL, |
| | AND BTU'S. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ENERGY C404.7.1 |
| | POOL HEATERS. ALL POOL HEATERS SHALL MEET THE MINIMUM |
| | EFFICIENCY LISTED FOR THAT TYPE OF POOL HEATER IN TABLE |
| | C404.2 AND BE EQUIPPED WITH A READILY ACCESSIBLE ON-OFF |
| | SWITCH THAT IS MOUNTED OUTSIDE OF THE HEATER TO ALLOW |
| | SHUTTING OFF THE HEATER WITHOUT ADJUSTING THE |
| | THERMOSTAT SETTING.. CONTRACTOR IS TO SUBMIT HEATER |
| | SPECS TO THE ENGINEER OF RECORD FOR REVIEW AND SIGN OFF |
| | ON THE SHOP DRAWING FOR APPROVAL BEFORE SUBMITTAL TO |
| | THE BUILDING DEPARTMENT. |
| | |
| | 4) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ENERGY C404.7.1 |
| | POOL HEATERS. GAS-FIRED HEATERS SHALL NOT BE EQUIPPED |
| | WITH CONSTANT BURNING PILOT LIGHTS. |
| | . CONTRACTOR IS TO SUBMIT HEATER SPECS TO THE ENGINEER |
| | OF RECORD FOR REVIEW AND SIGN OFF ON THE SHOP DRAWING |
| | FOR APPROVAL BEFORE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT. |
| | |
| | 5-9) COMPLIED. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |