| 2015-12-31 09:31:26 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15120024 |
| | ADD: 312 23RD ST. |
| | CONT: ROYAL PALM POOLS |
| | TEL: 561-798-3711 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: THURS. DEC.31/2015 |
| | ACTION: DENIED |
| | |
| | 1) THERE IS A DISCREPANCY IN THE MATER BUILDING PERMIT |
| | 14120431 AND THE LAY OUT OF THE POOL PERMITED SET OF |
| | PLANS. THE MATER BUILDING PERMIT SHOWS THE STAIRS ON |
| | THE WEST END OF THE POOL (SEE SHEETS A-2.00 & A-3.40) |
| | WHERE AS THE SUBMITTED POOL PLANS INDICATE THE STAIRS |
| | AND SHALLOW END OF THE POOL AT THE EAST END OF THE |
| | POOL. DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2) SHEET 4 OF 4 POOL EQUIPMENT NOTE 11 INDICATES THERE |
| | IS TO BE A POOL GAS FIRED HEATER. SPEC SHEET SUBMITTED |
| | IS FOR MASTERTEMP HEATERS A GENERIC SPEC SHEET OF THEIR |
| | PRODUCTS. PLEASE IDENTIFY WHICH OF THEIR PRODUCTS |
| | (MODEL), GAS TYPE PROPANE OR NATURAL, AND BTU'S. 2014 |
| | FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ENERGY C404.7.1 |
| | POOL HEATERS. ALL POOL HEATERS SHALL MEET THE MINIMUM |
| | EFFICIENCY LISTED FOR THAT TYPE OF POOL HEATER IN TABLE |
| | C404.2 AND BE EQUIPPED WITH A READILY ACCESSIBLE ON-OFF |
| | SWITCH THAT IS MOUNTED OUTSIDE OF THE HEATER TO ALLOW |
| | SHUTTING OFF THE HEATER WITHOUT ADJUSTING THE |
| | THERMOSTAT SETTING. |
| | |
| | 4) PLEASE SHOW COMPLIANCE WITH 2014 FBC-ENERGY C404.7.1 |
| | POOL HEATERS. GAS-FIRED HEATERS SHALL NOT BE EQUIPPED |
| | WITH CONSTANT BURNING PILOT LIGHTS. |
| | |
| | 5) SHEET 4 OF 4 THE POOL ELECTRIC DIAGRAM SHOWS THE |
| | POOL HEATER BUT THERE IS NO MENTION OF TIME SWITCHES OR |
| | OTHER CONTROL METHOD THAT CAN AUTOMATICALLY TURN OFF |
| | AND ON HEATERS AND PUMPS ACCORDING TO A PRESET SCHEDULE |
| | SHALL BE INSTALLED ON ALL HEATERS AND PUMPS. HEATERS, |
| | PUMPS AND MOTORS THAT HAVE BUILT IN TIMERS SHALL BE |
| | DEEMED IN COMPLIANCE WITH THIS REQUIREMENT. SHOW |
| | COMPLIANCE WITH 2014 FBC-ENERGY CODE C404.7.2. |
| | |
| | 6) PLEASE PROVIDE COMPLIANCE WITH SECTION OF THE 2014 |
| | FBC-ENERGY C404.7.3 COVERS. HEATED SWIMMING POOLS AND |
| | INGROUND PERMANENTLY INSTALLED SPAS SHALL BE EQUIPPED |
| | WITH A VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE |
| | OR A LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT |
| | LOSS. |
| | |
| | 7) SHEET 1 OF 4 SHOWS THE POOL SIZE OF 16 X 40 FEET OR |
| | 112 LINEAR FEET OF PERMITER. PLEASE NOTE THE MATER |
| | PERMIT WAS ISSUED AS A R2 OCCUPANCY THERE ARE AREAS OF |
| | THE PLANS THAT DEAL WITH FLORIDA ACCESSIBLITY AND AREAS |
| | THAT ARE STRICTLY FAIR HOUSING. IT IS NOT KNOWN WHAT |
| | THE FINAL USE WILL BE A CONDOMINIUM UNDER FAIR HOUSING |
| | OR IF IT MAY BE AN APARTMENT BUILDING (TRANSIENT) THAT |
| | COULD BE UNDER FLORIDA ACCESSIBLITY. THIS COMMENT MAY |
| | BE RELEVANT OR NOT DEPENDING ON THE FINAL USAGE. |
| | PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 454.1.2.5.6 |
| | DISABLED ACCESS. PERMANENT OR PORTABLE STEPS, RAMPS, |
| | HANDRAILS, LIFTS OR OTHER DEVICES DESIGNED TO |
| | ACCOMMODATE HANDICAPPED INDIVIDUALS IN SWIMMING POOLS |
| | MAY BE PROVIDED. LIFTS MOUNTED INTO THE POOL DECK SHALL |
| | HAVE A MINIMUM 4-FOOT-WIDE (1219 MM) DECK BEHIND THE |
| | LIFT MOUNT. |
| | |
| | 2015 FBC-ACCESSIBILITY CODE 242.2 SWIMMING POOLS. |
| | AT LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE |
| | PROVIDED FOR SWIMMING POOLS. ACCESSIBLE MEANS OF ENTRY |
| | SHALL BE SWIMMING POOL LIFTS COMPLYING WITH 1009.2; |
| | SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER WALLS |
| | COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING WITH |
| | 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT LEAST |
| | ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL COMPLY |
| | WITH 1009.2 OR 1009.3. |
| | |
| | EXCEPTIONS: 1. WHERE A SWIMMING POOL HAS LESS THAN 300 |
| | LINEAR FEET (91 M) OF SWIMMING POOL WALL, NO MORE THAN |
| | ONE ACCESSIBLE MEANS OF ENTRY SHALL BE REQUIRED |
| | PROVIDED THAT THE ACCESSIBLE MEANS OF ENTRY IS A |
| | SWIMMING POOL LIFT COMPLYING WITH 1009.2 OR SLOPED |
| | ENTRY COMPLYING WITH 1009.3. |
| | |
| | 2014 FBC-ACCESSIBILITY 1009.1 GENERAL. WHERE PROVIDED, |
| | POOL LIFTS, SLOPED ENTRIES, TRANSFER WALLS, TRANSFER |
| | SYSTEMS, AND POOL STAIRS SHALL COMPLY WITH 1009. |
| | |
| | 8) PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 454.1.3.3.1 |
| | REQUIRED SAFETY EQUIPMENT. |
| | |
| | 9) SHEET 1 OF 4 SHOWS A LARGE POOL EQUIPMENT ROOM. |
| | CONCERNS ARE COMPLYING WITH : |
| | 9A) 2014 FBC-B 454.1.5.4 VENTILATION. EQUIPMENT ROOMS |
| | SHALL HAVE EITHER FORCED DRAFT OR CROSS VENTILATION. |
| | ALL BELOW-GRADE EQUIPMENT ROOMS SHALL HAVE A STAIRWAY |
| | ACCESS WITH FORCED DRAFT VENTILATION OR A FULLY |
| | LOUVERED DOOR AND POWERED INTAKE WITHIN 6 INCHES (152 |
| | MM) OF THE FLOOR. |
| | |
| | 9B) 2014 FBC-B 454.1.5.8 STORAGE. EQUIPMENT ENCLOSURES, |
| | ROOMS OR AREAS SHALL NOT BE USED FOR STORAGE OF |
| | CHEMICALS EMITTING CORROSIVE FUMES OR FOR STORAGE OF |
| | OTHER ITEMS TO THE EXTENT THAT ENTRANCE TO THE ROOM FOR |
| | INSPECTION OR OPERATION OF THE EQUIPMENT IS IMPAIRED. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |