2015-12-08 08:23:041ST REVIEW 2014 MECHANICAL
 PERMIT #15111037
 12/8/15
  
 1) SHEET M5.1: OUTDOOR AIR CALCULATIONS FOR THE AC
 SYSTEMS OPERATING ON THE 2ND FLOOR ARE IN THE SCHEDULE,
 HOWEVER NO AC PLANS FOR THE 2ND FLOOR ARE INCLUDED IN
 THE PLAN SETS: PLEASE PROVIDE THE PLANS.
 2) M1.2 AND M5.1: PLEASE LABEL THE OFFICE ROOMS ON THE
 AC PLANS TO MATCH THE LABELING IN THE O/A SCHEDULE.
 3) M1.2 AND M5.1: THE O/A SCHEDULE INDICATES AIR BEING
 PROVIDED TO CORRIDOR 5 IN SUITE 601, HOWEVER THERE ARE
 NO AC DROPS SHOWN IN THE LAYOUT PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER