| Plan Review Notes For Permit 15111032 |
| Permit Number |
15111032 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-04-29 14:25:16 | 3RD REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: IT APPEARS GAS COMMENTS FROM SECOND | | | REVIEW WERE NOT ADDRESSED | | | | | | 2ND REQUEST | | | 1. SHT. P103 SYSTEM IS INDICATED AS 2PSI PLEASE SHOW | | | STEP DOWN REGULATORS FOR ALL APPLIANCES SHALL COMPLY | | | WITH FBC FUEL GAS SEC. 410.1-410.2 | | | 2. SHT. P103 PE PIPING IS NOT ALLOWED TO BE INSTALLED | | | IN A STRUCTURE PER FBC FUEL GAS SEC. 404.17.1 | | | 3.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | THE RESPONSE YOU GAVE ON FIRST REVIEW SEE P103 DOES NOT | | | COMPLY | | | 4.SHT. P103 SHOW LENGTH OF PIPE FROM METER TO FIRST | | | BRANCH PER .FUEL GAS CODE SEC. 402.4.1. |
|