| 2016-03-28 17:58:51 | NEW SINGLE FAMILY RESIDENCE (R3), ROOFING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY |
| | IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. AND, |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| | SELECTED ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN |
| | PRESSURES. |
| | |
| | RESPONSE: THE SELECTED ASSEMBLY (W-55) FROM FLORIDA |
| | PRODUCT APPROVAL FL5680-R15 IS GOOD FOR -60PSF. NEED TO |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL |
| | ENHANCEMENT AT PERIMETER AND CORNER AREAS AS REQUIRED |
| | BY NOTE #8 ON PAGE 2 OF 76 OF PRODUCT APPROVAL |
| | SUBMITTED. |
| | NOTE: FORM 100 SUBMITTED IS FOR PBC BUILDING |
| | DEPARTMENT. THIS IS NOT USED BY THE CITY OF WPB. |
| | |
| | B) MODIFIED MEMBRANE THAT IS DESIGNED TO RECEIVE THE |
| | FINISH MATERIAL SPECIFIED ON PLANS FOR THE TERRACES AND |
| | BALCONIES. NOTE: CHECK DESIGN PRESSURES FOR SELECTED |
| | ASSEMBLY. SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE |
| | REQUIRED. |
| | |
| | RESPONSE: ACCORDING TO CONDITIONS OF USE SEC. 5.2 OF |
| | ICC ESR-2467 REPORT SUBMITTED, THIS PRODUCT IS FOR |
| | INTERIOR USE ONLY. NEED PRODUCT APPROVAL FOR EXTERIOR |
| | USE AND NEED TO CONSIDER THE WIND LOADS. |
| | |
| | 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |