| 2016-03-18 16:47:26 | |
| | PLUMBING COMMENTS; |
| | |
| | 1.YOUR RESPONSE TO PREVIOUS COMMENT #2 DOES NOT COMPLY |
| | WITH CODE . WHERE YOU HAVE A HYDRAULIC ELEVATOR PIT YOU |
| | SHALL COMPLY WITH FBC PL SEC. 1003.4 OIL SEPARATORS |
| | REQUIRED. |
| | AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES |
| | WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND |
| | IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE |
| | INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR |
| | FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING |
| | INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF |
| | DISPOSAL. |
| | |
| | EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN |
| | HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM |
| | IS INSTALLED. |
| | |
| | 2. SHT.104 A RECIRCULATION SYSTEM IS REQUIRED TO COMPLY |
| | WITH FBC PL SEC. 607.2 HOT OR TEMPERED WATER SUPPLY TO |
| | FIXTURES. |
| | THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, |
| | FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT |
| | REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET |
| | (15 240 MM). RECIRCULATING SYSTEM PIPING AND |
| | HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| | HOT OR TEMPERED WATER. |
| | |
| | 3. SHT. P102 SOIL STACK FOR BATHROOMS 208+212 SHALL |
| | CONNECT TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP |
| | 108 TO COMPLY WITH FBCR SEC. P3108.1 |
| | |
| | 4. SHT P104 THE COLD WATER MAIN SUPPLY APPEARS TO BE |
| | UNDERSIZED SHALL COMPLY WITH FBCR SEC. P2903 |
| | |
| | 5. SHT,P102 THE MODEL ON THE MANUFACTURE SPEC FOR |
| | TANKLESS HEATER DOES NOT MATCH THE ONE ON P104 PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |