| 2016-03-28 18:30:32 | NEW SINGLE FAMILY RESIDENCE (R3), SECOND MECHANICAL |
| | REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- RE-SUBMITTED SET OF PLANS IS MISSING DRAWINGS M201 |
| | AND M301. NEED COMPLETE SET OF DRAWINGS. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 2- MECHANICAL ENGINEER OF RECORD TO PROVIDE EQUIPMENT |
| | SIZING CALCULATIONS AS REQUIRED BY SEC. R403.6.1 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | RESPONSE: RESPONSE LETTER STATES THAT "SECTION R403 IS |
| | NOT VALID CODE REFERENCE FOR ENERGY CODE". THIS IS |
| | INCORRECT. SEE SEC. R403.6.1 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | ALSO, THE ENGINEER IS CITING EXCEPTION #2 OF SEC. |
| | R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014) TO DO A SUMMARY SHEET. THIS IS INCORRECT ALSO. |
| | THE EXCEPTION #2 APPLIES TO ATTACHED SINGLE AND |
| | MULTIPLE FAMILY UNITS ONLY. THIS IS A DETACHED SINGLE |
| | FAMILY RESIDENCE. THEREFORE, NEED TO PROVIDE COMPLETE |
| | EQUIPMENT SIZING CALCULATIONS USING AN APPROVED HEATING |
| | AND COOLING CALCULATION METHODOLOGIES BASED ON THE |
| | BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE |
| | BUILDING AND PROVIDE THE MANUFACTURER AND MODEL NUMBER |
| | OF THE OUTDOOR AND INDOOR UNITS AS REQUIRED BY SEC. |
| | R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | 3- SHEET M302: UPDATE THE CODES AND STANDARDS |
| | INFORMATION. THE CURRENT CODE IS THE FBC-RESIDENTIAL, |
| | 5TH EDITION (2014) NOT 2010 FBC. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD |
| | DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |