| 2016-03-17 18:38:43 | JOB PERMIT NUMBER: 15111032 |
| | JOB ADDRESS: 2914 WASHINGTON RD |
| | WEST PALM BEACH FLORIDA |
| | DATE: MARCH 17 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, |
| | SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET |
| | SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE |
| | SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED WITHIN 25 FT. OF THE EQUIPMENT. MISSING ON |
| | SHEET E100 BY CU#1 |
| | - PROVIDE SERVICE EQUIPMENT LOCATION ON ELECTRICAL |
| | FLOOR PLANS. WBA 107 |
| | - GARAGE DOOR MOTOR OUTLET A 15 , A 17 MUST BE GFCI |
| | PROTECTED NEC 210.8A |
| | - GENERATOR ON A SEPARATE PERMIT TO INCLUDE CUT SHEETS |
| | OF ATS EQUIPMENT ( SERVICE-RATED ) AND GENERATOR |
| | MANUFACTURE SPECS. |
| | - RISER DIAGRAM ON SHEET E102 STILL SHOWS SERVICE |
| | GROUNDED CONDUCTOR BEING IN PARALLEL BY RUNNING A # 4 |
| | AWG BONDING CONDUCTOR THIS IS A VIOLATION OF NEC 250 |
| | GROUNDING & BONDING PLUS NEC 310.10 H WIRING METHODS. |
| | - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING STRIP |
| | NEC 250.94 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |