| 2016-01-04 17:54:14 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6700 |
| | [email protected] |
| | ALTERNATE CONTACT |
| | MIKE ALBARRAN |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |
| | GENERATOR ON SEPERATE PERMIT. POOL ON A SEPERATE |
| | PERMIT. |
| | FBC E C405.7.3.1 FEEDERS AND CUSTOMER OWNED SERVICE |
| | CONDUCTORS. |
| | FEEDER AND CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE |
| | SIZED FOR A MAXIMUM VOLTAGE DROP OF 2 PERCENT AT DESIGN |
| | LOAD. |
| | C405.7.3.2 BRANCH CIRCUITS. |
| | BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM |
| | VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD. |
| | 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY |
| | HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS |
| | SHALL |
| | BE PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. |
| | SUCH A |
| | DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE |
| | BUILDING |
| | OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL |
| | CALCULATED |
| | LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS |
| | USED, THE CALCULATED LOAD AFTER APPLYING DEMAND |
| | FACTORS, |
| | AND THE SIZE AND TYPE OF CONDUCTORS TO BE USED. |
| | SHEET E 102 SHOWS A 2 INCH CONDUIT FOR 3 350 KCMIL |
| | THATS INADEQUATE CHECK TABLE 9 AND ANNEX C |
| | ALSO SHOWS A # 4 BONDING CONDUCTOR WHICH WOULD INDICATE |
| | PARRELLELING GROUNDED CONDUCTOR VIOLATION OF |
| | NEC 250 AND 300 WIRING METHODS. PLEASE SPECIFY |
| | CONDUCTOR AND CONDUIT TYPE ON RISER DIAGRAM. ( PANEL B |
| | , C , PE. ) |
| | PLEASE SHOW SERVICE EQUIPMENT ON SITE / FLOOR PLANS |
| | PROVIDE STEAMER AND ELEVATOR SPECS DON'T SEE ON PANEL |
| | SCHEDULE ? |
| | SUB PANEL PE IS MARKED AS CIRCUIT 19 , 21 DOESN'T |
| | CORRESPOND WITH PANEL SCHEDULE 33, 35 ? |
| | |
| | |
| | 406.12 TAMPER-RESISTANT RECEPTACLES FOR DWELLING UNITS. |
| | IN ALL AREAS SPECIFIED IN 210.52, ALL NONLOCKING-TYPE |
| | 125-VOLT, 15- AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT RECEPTACLES. |
| | 210.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | (A) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND |
| | 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED |
| | IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION |
| | ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS |
| | SHALL |
| | BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER, |
| | COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF |
| | THE |
| | BRANCH CIRCUIT. |
| | SMOKE ALARMS / CARBON MONOXIODE REQUIRED PER |
| | RESIDENTIAL CODE SECTIONS 314 / 315 |
| | FBC ER C405 75 % OF LIGHTING SHALL BE HIGH EFFICIENCY . |
| | ALL RECCESSED FIXTURE SHALL BE |
| | IC RATED AND SEALED TYPE. |
| | GARARGE DOOR OPENERS AREN'T GFCI PROTECTED NEC 210.8 |
| | NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN |
| | 25? OF MECHANICAL EQUIPMENT. |
| | DISCONNECTS FOR COMPRESSOR UNITS SEEM TO BE BEHIND |
| | EQUIPMENT NEC 110.26 WORKING SPACE CLEARANCE. |
| | |
| | |