| Plan Review Notes For Permit 15111031 |
| Permit Number |
15111031 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-16 10:49:42 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15111031 | | | 2/16/16 | | | | | | 1) THE SUBMITTED AC CALCULATIONS ARE BASED ON DESIGN | | | TEMPERATURES FROM MIAMI FL. PLEASE REVISE THE | | | CALCULATIONS USING DESIGN TEMPERATURES FROM WEST PALM | | | BEACH- REFER TO ACCA MANUAL N- SEE SECTION C403.2.1 | | | FBC-14 ENERGY CONSERVATION | | | 2) PLEASE INDICATE THE DIRECTIONAL ORIENTATIONS OF THE | | | TENANT SPACES ON THE AC CALCULATIONS- SECTION C403.2.1. | | | 3) PLEASE PROVIDE AC EQUIPMENT SCHEDULES ON THE PLAN- | | | THE IS NO WAY TO VERIFY THE COMPLIANCE DATA FOR THE | | | SYSTEMS LISTED IN THE SUBMITTED ASHRAE 90.1 ENERGY COST | | | BUDGET OPTION FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|