Plan Review Notes
Plan Review Notes For Permit 15111031
Permit Number 15111031
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-06 11:56:251ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.WATER FOUNTAINS ARE REQUIRED PER FBC PL SEC 404.1 AND
 TABLE 403.1. SHALL COMPLY WITH FBC ACC. SEC 602
 2.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION. PER FBC ACC SEC 604.2
 3. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE TO FINISHED FLOOR. PER FBC ACC. SEC
 609.4
 4.HOT WATER OR TEMPERED WATER SHALL BE SUPPLIED FOR
 BATHING AND WASHING PURPOSES INCLUDING HAND WASHING
 .PER FBC PL SEC.607.1