| 2015-12-01 16:44:10 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15111031 | | | 12/1/15 | | | | | | 1) PROVIDE AC COOLING AND HEATING LOAD CALCULATIONS IN | | | ACCORDANCE WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL | | | N- SEE SECTION C303.2.1 FBC-14 ENERGY CALCULATIONS. | | | 2) THE PLANS INDICATES A CHANGE IN OCCUPANCY | | | CLASSIFICATION FROM THE PREVIOUS ASSEMBLY OCCUPANCY TO | | | FOUR NEW MERCANTILE OCCUPANCIES- COMPLIANCE WITH THE | | | FBC-14 ENERGY CONSERVATION CODE IS REQUIRED. PLEASE SEE | | | SECTION C101.4.4 AND SUBMIT EITHER THE PRESCRIPTIVE | | | COMPLIANCE FORM R402, OR THE ENERGY GAUGE PERFORMANCE | | | BASED FORM 506-2014. | | | 3) SHEET A-8: THE DOOR SCHEDULE INDICATES WOOD LOUVERED | | | DOORS FOR THE NEW AIR HANDLER CLOSETS- REFER TO SECTION | | | 602 FBC-14 MECHANICAL, AND C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION AND PROVIDE NON-COMBUSTIBLE DOORS. | | | 4) M-1: PROVIDE TOILET ROOM EXHAUST DUCT DETAILS OR | | | NOTES FOR RETAIL SPACES #2 & #3. | | | 5) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR TIE | | | DOWN OF THE CONDENSERS TO THE EXISTING STANDS- SEE | | | SECTION 301.15 FBC-14 MECHANICAL. | | | 6) M-2: THE MINIMUM 18" SPACING BETWEEN THE CONDENSERS | | | ON THE ROOF STANDS MUST BE VERIFIED TO BE IN ACCORDANCE | | | WITH THE MANUFACTURER'S RECOMMENDATIONS- PLEASE SUBMIT | | | DOCUMENTATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|