Plan Review Notes
Plan Review Notes For Permit 15111031
Permit Number 15111031
Review Stop M
Sequence Number 1
Notes
Date Text
2015-12-01 16:44:101ST REVIEW 2014 MECHANICAL
 PERMIT #15111031
 12/1/15
  
 1) PROVIDE AC COOLING AND HEATING LOAD CALCULATIONS IN
 ACCORDANCE WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL
 N- SEE SECTION C303.2.1 FBC-14 ENERGY CALCULATIONS.
 2) THE PLANS INDICATES A CHANGE IN OCCUPANCY
 CLASSIFICATION FROM THE PREVIOUS ASSEMBLY OCCUPANCY TO
 FOUR NEW MERCANTILE OCCUPANCIES- COMPLIANCE WITH THE
 FBC-14 ENERGY CONSERVATION CODE IS REQUIRED. PLEASE SEE
 SECTION C101.4.4 AND SUBMIT EITHER THE PRESCRIPTIVE
 COMPLIANCE FORM R402, OR THE ENERGY GAUGE PERFORMANCE
 BASED FORM 506-2014.
 3) SHEET A-8: THE DOOR SCHEDULE INDICATES WOOD LOUVERED
 DOORS FOR THE NEW AIR HANDLER CLOSETS- REFER TO SECTION
 602 FBC-14 MECHANICAL, AND C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND PROVIDE NON-COMBUSTIBLE DOORS.
 4) M-1: PROVIDE TOILET ROOM EXHAUST DUCT DETAILS OR
 NOTES FOR RETAIL SPACES #2 & #3.
 5) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR TIE
 DOWN OF THE CONDENSERS TO THE EXISTING STANDS- SEE
 SECTION 301.15 FBC-14 MECHANICAL.
 6) M-2: THE MINIMUM 18" SPACING BETWEEN THE CONDENSERS
 ON THE ROOF STANDS MUST BE VERIFIED TO BE IN ACCORDANCE
 WITH THE MANUFACTURER'S RECOMMENDATIONS- PLEASE SUBMIT
 DOCUMENTATION.
  