| 2016-01-06 19:22:05 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. NEC 300.21 SPREAD OF FIRE OR PRODUCTS OF COMBUSTION. |
| | OPENINGS AROUND ELECTRICAL PENETRATIONS INTO OR THROUGH |
| | FIRE-RESISTANT-RATED WALL, PARTITIONS, FLOORS OR |
| | CEILINGS SHALL BE FIRE-STOPPED USING APPROVED METHODS |
| | TO MAINTAIN THE FIRE RESISTANCE RATING. SEE FBC-B |
| | SECTION 714. |
| | 2. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| | 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| | ?WR?. |
| | 3. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| | BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| | LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| | OWN CIRCUIT. |
| | 4. STAIRS SHALL BE PROVIDED WITH EMERGENCY |
| | ILLUMINATION. |
| | 5. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | 6. NEC 300.50 UNDERGROUND INSTALLATIONS. (F) WHERE A |
| | RACEWAY ENTERS FROM AN UNDERGROUND SYSTEM, THE ENDS |
| | SHALL BE SEALED WITH A LISTED COMPOUND TO PREVENT THE |
| | ENTRANCE OF MOISTURE OR GASES CONTACTING LIVE PARTS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |