| Plan Review Notes For Permit 15111031 |
| Permit Number |
15111031 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-12-05 14:57:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. A5, AREA PER OCCUPANT CANNOT BE LESS THAN THE TABLE, | | | FBC 5TH ED. TABLE 1004. 100 SF PER OCCUPANT SHOWN; | | | MERCANTILE REQUIRES 30 SF PER OCCUPANT MAX; REVISE. | | | | | | 2. A2, THIS IS A CHANGE OF OCCUPANCY FROM ASSEMBLY TO | | | MERCANTILE. INCORPORATE THIS INTO THE PLAN AND SHOW | | | COMPLIANCE WITH REQUIREMENTS OF FBC 5TH EDITION | | | EXISTING BUILDING CHAPTER 10. | | | | | | 3. ADVISORY ONLY: PRODUCT APPROVALS REVIEWED BY | | | DESIGNER OF RECORD ARE REQUIRED FOR THE MECH STAND, | | | STOREFRONT, AND DOORS. THEY ARE TO BE SUBMITTED, | | | REVIEWED AND APPROVED PRIOR TO INSTALLATION. | | | | | | |
|