| 2015-12-17 16:14:03 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | | | | PROVISO | | | | | | (B) WET LOCATIONS. THE INTERIOR OF ENCLOSURES OR | | | RACEWAYS | | | INSTALLED UNDERGROUND SHALL BE CONSIDERED TO BE A WET | | | LOCATION. | | | INSULATED CONDUCTORS AND CABLES INSTALLED IN THESE | | | ENCLOSURES | | | OR RACEWAYS IN UNDERGROUND INSTALLATIONS SHALL BE | | | LISTED FOR USE | | | IN WET LOCATIONS AND SHALL COMPLY WITH 310.10(C). ANY | | | CONNECTIONS | | | OR SPLICES IN AN UNDERGROUND INSTALLATION SHALL BE | | | APPROVED | | | FOR WET LOCATIONS. | | | | | | (1) GENERAL. IN INDOOR LOCATIONS OTHER THAN DWELLINGS | | | AND | | | ASSOCIATED ACCESSORY STRUCTURES, FLUORESCENT LUMINAIRES | | | THAT UTILIZE | | | DOUBLE-ENDED LAMPS AND CONTAIN BALLAST(S) THAT CAN BE | | | SERVICED IN PLACE SHALL HAVE A DISCONNECTING MEANS | | | EITHER INTERNAL | | | OR EXTERNAL TO EACH LUMINAIRE. FOR EXISTING INSTALLED | | | LUMINAIRES | | | WITHOUT DISCONNECTING MEANS, AT THE TIME A BALLAST IS | | | REPLACED, A DISCONNECTING MEANS SHALL BE INSTALLED. THE | | | LINE | | | SIDE TERMINALS OF THE DISCONNECTING MEANS SHALL BE | | | GUARDED. |
|