2018-07-09 16:36:10PROVISO 4-1 WAS RESOLVED UNDER SUBMITTAL 17110020 (REG)
2017-02-06 14:01:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR.
 CONT: SUFFOLK CONSTRUCTION CO.
 TEL: 561-832-1616
 E-MAIL: [email protected] / ED HANRATTY
  
 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 5TH REVIEW
 DATE: MON. FEB. 06/ 2017
 ACTION:BUILDING PROVISO
  
  
 NOTE: THIS REVIEW IS GOING TO BE COMPLETED AS A MIXED
 USE BUILDING,(FEMA REGULATIONS) AND THE REQUIREMENTS AS
 SUCH. 2010 FBC-B 1612.4 DESIGN & CONSTRUCTION SHALL BE
 IN ACCORDANCE WITH ASCE 24-05. ASCE 24-05 TABLE 6-1
 MINIMUM ELEVATION OF FLOODPROOFING, RELATIVE TO THE
 BASE FLOOD (BFE) OR DESIGN FLOOD ELEVATION (DFE)-
 OUTSIDE OF HIGH RISK FLOOD HAZARD AREAS. STRUCTURE
 CATEGORY- II (FOOTNOTE) C. (C) DRY FLOODPROOFING OF
 RESIDENTIAL BUILDINGS AND RESIDENTIAL PORTIONS OF MIXED
 USE BUILDINGS SHALL NOT BE PERMITTED.
  
  
 1) BUILDING PROVISO: DEFERRED SUBMITTAL. ELEVATOR
 PRODUCT DATA SHEET FOR OTIS GEN 2 ELEVATOR.
  
 FEMA TECHNICAL BULLETIN 4-93. FEMA REGULATION
 60.3(A)(3) IF A PROPOSED BUILDING SITE WILL BE
 REASONABLY SAFE FROM FLOODING. IF A PROPOSED BUILDING
 SITE IS IN A FLOOD PRONE AREA, ALL NEW CONSTRUCTION AND
 SUBSTANTIAL IMPROVEMENTS SHALL? BE CONSTRUCTED WITH
 MATERIALS RESISTANT TO FLOOD DAMAGE,(III) BE
 CONSTRUCTED BY METHODS AND PRACTICES THAT MINIMIZE
 FLOOD DAMAGES, AND (IV) BE CONSTRUCTED WITH
 ELECTRICAL... EQUIPMENT AND OTHER SERVICES FACILITIES
 THAT ARE DESIGNED AND / OR LOCATED SO AS TO PREVENT
 WATER DAMAGE FROM ENTERING OR ACCUMULATING WITHIN THE
 COMPONENTS DURING CONDITIONS OF FLOODING.
 TO KEEP THE ELEVATOR CABS FROM HAVING SUBSTANTIAL
 DAMAGE FROM FLOODWATERS, IS THERE A INTERLOCKING
 CONTROL OR FLOAT SWITCH THAT WHEN ACTIVATED WILL KEEP
 THE CAB FROM DESCENDING INTO THE FLOODWATERS.
  
 2) PROVISO: ANY EUROPEAN CAR LIFT SYSTEM WILL NEED TO
 SUBMIT PRODUCT LISTINGS WHERE THEY HAVE AN NRTL
 (NATIONALLY RECOGNIZED TESTING LABORATORY) ACCREDITED
 BY THE US AUTHORITY OCCUPATIONAL SAFETY AND HEALTH
 ADMINISTRATION AND STAMPED FOR US MARKETS.
  
 3) BUILDING PROVISO: THE PLANS SHOW AT THE ENTRY LEVEL
 OF THE LOBBY A RECEPTION/ REGISTRATION DESK. PLEASE
 PROVIDE COMPLIANCE WITH FAIR HOUSING SPECIFICATION OF
 ANSI 4.31 ALSO SEE REACH RANGES.
  
 4) BUILDING PROVISO: DEFERRED SUBMITTALS : TEST REPORTS
 SHOWING COMPLIANCE WITH:
  
 4)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 4)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 4)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) BUILDING PROVISO: DEFERRED SUBMITTALS: SHEET
 431-M4-01 MECHANICAL DETAILS EQUIPMENT SUPPORT CURB
 DETAIL & THYBAR VIBRATION CURB III DETAIL FOR OAU-1 &
 2. PLEASE PROVIDE THE PRODUCT APPROVALS FOR CURB
 DETAILS. TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF
 RECORD, AND WITH THEIR SHOP DRAWING STAMP OF APPROVAL.
 PLEASE NOTE THE STRUCTURAL ANCHOR TO THE BASE OR
 SUPPORT AS WELL AS THE UNIT TO THE CURB FOR MOMENT OF
 OVERTURNING, WILL NEED TO BE DESIGNED BY THE STRUCTURAL
 ENGINEER OR HIS DELEGATE WITH THE STRUCTURAL ENGINEERS
 APPROVAL BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT
 FOR REVIEW.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 6)BUILDING PROVISO: DEFERRED SUBMITTAL FOR
 ARCHITECTURAL TRIM AND EMBELLISHMENTS METAL FINS ON
 LEVEL 26. 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR
 AN ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE
 BUILDING OFFICIAL TO VERIFY COMPLIANCE WITH THE
 REQUIREMENTS OF CHAPTER 16 FOR WIND LOADS. 1407.6
 WEATHER RESISTANCE. IF DELEGATED ENGINEERING THEN THE
 DOCUMENTS NEED TO BE FORWARDED TO THE ENGINEER OF
 RECORD FOR REVIEW AND APPROVAL BEFORE SUBMITTING TO THE
 BUILDING DEPARTMENT. 61G15-30.003.
  
 7) BUILDING PROVISO: DEFERRED SUBMITTAL FOR THE TERRA
 COTTA WALL CLADDING UNITS. FOR ARCHITECTURAL TRIM AND
 EMBELLISHMENTS THE TERRA COTTA UNITS WILL NEED TO
 COMPLY WITH 2010 FBC-B 1407.5 APPROVAL. RESULTS OF
 APPROVED TESTS OR AN ENGINEERING ANALYSIS SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO VERIFY COMPLIANCE
 WITH THE REQUIREMENTS OF CHAPTER 16 FOR WIND LOADS.
 1407.6 WEATHER RESISTANCE. IF DELEGATED ENGINEERING
 THEN THE DOCUMENTS NEED TO BE FORWARDED TO THE ENGINEER
 OF RECORD FOR REVIEW AND APPROVAL BEFORE SUBMITTING TO
 THE BUILDING DEPARTMENT. 61G15-30.003.
  
 8) BUILDING PROVISO: DEFERRED SUBMITTAL
 POLYISOCYANURATE BOARD. WITH SINGLE PLY RECOVERY BOARD
 AND SINGLE PLY PVC ROOFING MEMBRANE ROOFING. PLEASE
 PROVIDE THE PRODUCT APPROVALS FOR EACH OF THE MEMBERS.
 FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 9)BUILDING PROVISO: DEFERRED SUBMITTALS. DETAILS 3 & 4
 BOTH SHOW A TILE DECK ABOVE THE ROOFING SYSTEM. THE
 ROOFING SYSTEM WELL NEED TO PROVIDE PRODUCT APPROVALS
 FOR WIND AS WELL AS ENGINEERING FOR THE TILE DECK
 INSTALLATION THEY WILL MEET THE WIND LOADS FOR THE
 LOCATION ON THE BUILDING.2010 FBC-B COMPONENTS AND
 CLADDING. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 10) BUILDING PROVISO: DEFERRED SUBMITTAL. CANOPY
 SYSTEMS. ADDITIONAL ENGINEERING SHEETS (SHOP DRAWINGS)
 TO BE SUBMITTED AS A DEFERRED SUBMITTAL. PLEASE ALSO
 PROVIDE HOW CODE COMPLIANCE WITH 2010 FBC-B 2405.2
 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS WILL BE
 COMPLIED WITH. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 11) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, INTAKE AND
 EXHAUST FANS ?
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  