Plan Review Notes
Plan Review Notes For Permit 15111020
Permit Number 15111020
Review Stop M
Sequence Number 4
Notes
Date Text
2017-01-30 11:06:024TH REVIEW FBC-2014 MECHANICAL
 PERMIT #15111020
 1/27/17
  
 THE FOLLOWING LIST OF COMMENTS FROM THE 3RD REVIEW
 STILL EXIST OR HAVE NOT BEEN ADDRESSED IN ENTIRETY.
  
 1) COMMENT #1: THE REVISED PLANS UPLOADED ON 1/20/2017
 HAVE ELECTRONIC SEALS AND SIGNATURES. ALL OTHER
 EXISTING PLAN SHEETS DO NOT.
  
 2) COMMENT #3: THE REVISED ENERGYGAUGE COMPLIANCE MUST
 BE ELECTRONICALLY SIGNED AND SEALED.
  
 3) COMMENT #5: PLAN SHEETS M2.0P1, M2.0P2, & M6.02 HAVE
 NOT BEEN REVISED PER THE COMMENTS OR NARRATIVE
 RESPONSE.
  
 4) COMMENT #8, M2.0P1: REQUESTED SEPARATION DISTANCE
 BETWEEN THE GENERATOR AIR INTAKE AND EXHAUST NOT
 PROVIDED.
  
 5) COMMENT #9, M2.0P1: REQUESTED MOTORIZED DAMPERS FOR
 O/A DUCTS TO GUESTROOMS.
  
 6) COMMENT #11, M6.02: FAN SCHEDULE NOTES NOT UPDATED.
  
 7) COMMENT #12, M5.04: PRINT ON PLAN SHEET STILL FAINT
 AND ILLEGIBLE.
  
 8) COMMENT #13, M6.02: SCHEDULE NOT UPDATED TO PROVIDE
 CORRECT NOTES AND NOA #S.
  
 9) COMMENT #14, M2.0P1: PLAN NOT REVISED TO SHOW
 RELOCATION OF GARAGE EXHAUST FANS OVER STAIRWELL AS
 STATED IN THE RESPONSE NARRATIVE.
  
 10) COMMENT #17, M2.01: REQUESTED COMBUSTION AIR
 CALCULATIONS NOT PROVIDED.
  
 11) COMMENT #18, M2.01: REQUESTED AIR BALANCE
 CALCULATIONS NOT PROVIDED.
  
 12) COMMENT #21, M2.01: REQUESTED DEMAND CONTROLLED
 VENTILATION NOT SHOWN IN THE CLUB DINING ROOM.
  
 13) COMMENT #23, M2.02: ABOVE CEILING PLENUM SPACES NOT
 IDENTIFIED CLEARLY.
  
 14) COMMENT #25, M2.23: REQUESTED DUCTWORK NOT SHOWN.
  
 15) BELOW IS A LIST OF MISSING FIRE OR FIRE/SMOKE
 DAMPERS FOR DUCTS PENETRATING RATED WALLS. PLEASE
 PROVIDE THE DAMPERS FOR DUCTS WHERE REQUIRED, OR IF
 CLAIMING ANY EXCEPTIONS WRITTEN IN THE CODE, PLEASE
 PROVIDE THE SECTION NUMBER.
  
 * M2.0P2 NORTH CORE: 4X4 O/A DUCT PENETRATION RESIDENT
 STORAGE WALL
 * M2.0P2 EAST: 6X4 O/A DUCT PENETRATING STORAGE ROOM
 WALL AT EAST SIDE OF BUILDING.
 * M2.0P1: 4X4 O/A DUCT AT WATER FEATURE WALL
 * M2.0P1: 4X4 O/A DUCT AT MAINTENANCE WALL
 * M2.0P1: 6X6 O/A DUCT AT RESIDENT STORAGE
 * M2.0P1: 4X4 O/A DUCT AT CORRIDOR
 * M2.0P1: 6" FLEX DUCT AT STORAGE P116.
 * M2.0P1: 12X6 DUCT PENETRATING WALLS AT MEP/CAR
 WASH/DOG SPA.
 * M2.0P1: 12X12 EXHAUST DUCT AT DOG SPA.
 * M2.01: INTAKE OPENING AND EXHAUST OUTLET AT GENERATOR
 ROOM.
 * M2.01: EXHAUST DUCT AT MANICURE ROOM WALL.
 * M2.01: 8X6 O/A DUCT AT CORRIDOR
 * M2.02: 10X10 DUCT AT JANITOR/FIRE VEST. & FIRE
 VEST./ELEV. LOBBY.
 * M2.02: 26X12 DUCT AT MEP CLOSET.
 * M2.02 18X10 DUCT AT YOGA ROOM.
 * M2.03: TRANSFER DUCT AT CORRIDOR BY GUEST SUITE 11.
 PLEASE NOTE THAT THE CORRIDOR CANNOT BE USED AS A
 SUPPLY, RETURN, EXHAUST, RELIEF, OR AS A VENTILATION
 AIR DUCTS. SECTION 601.2.
 * M2.03: DUCTS PENETRATING RATED SHAFTS BY RESTROOMS IN
 GUEST SUITES 9, 10, & 11.
 * M2.05: SOUTH CORE- 18X10 DUCT IN STAIR #3 ENCLOSURE
 NOT PERMITTED AND NOT DAMPERED.
 * M2.05: NORTH CORE- TWO DUCTS SHOWN IN STAIR #1
 ENCLOSURE /UTILITY NOT PERMITTED/NOT DAMPERED.
 * M2.17, 18, 20, 21, 22: DUCTS NOT PERMITTED OR
 DAMPERED IN STAIR #3 ENCLOSURE.
 * M2.22: SOUTH CORE- 50X16 O/A DUCT AND 14X6 SUPPLY
 DUCT AT SHAFT.
 * M2.22 NORTH CORE- 16X8 AT SHAFT.
 * M2.23: NORTH CORE- NO DUCTS SHOWN IN DRAWING.
 * M2.24: SOUTH CORE- EXHAUST DUCTS PENETRATING SHAFTS.
 * M2.25: SOUTH CORE- 18X10 AT SHAFT.
 * M2.25: NORTH CORE: NO SIZE OR DAMPER FOR DUCT AT
 FIREMAN'S VEST./CORRIDOR WALL.
 * M2.26: SOUTH CORE: EXHAUST DUCT KEF #3 AT SHAFT.
 * M2.26: NORTH CORE: OA-1 DUCT AT SHAFT.
  
 16) IN ORDER TO EXPEDITE THE REVIEW OF THE SUBMITTED AC
 CALCULATIONS FOR THE APARTMENTS, PLEASE LABEL THE
 APARTMENT NUMBERS AND ZONES ON THE ENLARGED MECHANICAL
 FLOOR PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  