| 2017-01-30 10:48:26 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15111020 |
| | ADD: 1100 S. FLAGLER DR. |
| | CONT: SUFFOLK CONSTRUCTION CO. |
| | TEL: 561-832-1616 |
| | E-MAIL: [email protected] / ED HANRATTY |
| | |
| | 2010 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 4TH REVIEW |
| | DATE: MON. JAN. 30/ 2017 |
| | ACTION: DENIED |
| | |
| | |
| | NOTE: THIS REVIEW IS GOING TO BE COMPLETED AS A MIXED |
| | USE BUILDING,(FEMA REGULATIONS) AND THE REQUIREMENTS AS |
| | SUCH. 2010 FBC-B 1612.4 DESIGN & CONSTRUCTION SHALL BE |
| | IN ACCORDANCE WITH ASCE 24-05. |
| | ASCE 24-05 TABLE 6-1 MINIMUM ELEVATION OF |
| | FLOODPROOFING, RELATIVE TO THE BASE FLOOD (BFE) OR |
| | DESIGN FLOOD ELEVATION (DFE)- OUTSIDE OF HIGH RISK |
| | FLOOD HAZARD AREAS. STRUCTURE CATEGORY- II (FOOTNOTE) |
| | C. (C) DRY FLOODPROOFING OF RESIDENTIAL BUILDINGS AND |
| | RESIDENTIAL PORTIONS OF MIXED USE BUILDINGS SHALL NOT |
| | BE PERMITTED. |
| | |
| | 1) DENIED!!!!!!!! 2ND REQUEST!!!!!!. PLANS STILL SHOW |
| | AN OPENING WITHIN 10 FEET OF THE EXIT STAIR # 9. SEE |
| | 079-A2-0P1, 182-A5-28 & 182-A5-28 NOR THE STRUCTURAL |
| | SHEETS 358-S2-0P1. |
| | THE MECHANICAL SHEET 397-M2-)P1 SHOWS (2) FIRE DAMPERS |
| | PGEF P2-1A & PGP2-1B THESE FIRE DAMPERS DO NOT LINE UP |
| | OR ARE SIZED FOR THE EXTERIOR WALL OPENINGS SEPARATING |
| | THE EXTERIOR OF THE BUILDING. THE LAST DATE THIS PLAN |
| | WAS UPDATED WAS 11/22/2016. THE BRISTOL MEETING |
| | ADDRESSING THIS ISSUE WAS ON JAN 11/2017. |
| | , MECHANICAL REVIEW HAS ASKED THIS COMMENT REPEATEDLY |
| | SEE SHEET 182-A5-28 THE DETAILS SHOW 2 ISSUES: |
| | 1A) THE EXTERIOR EXIT STAIR SHOWS LOUVERS IN THE |
| | EXTERIOR WALL AND WITHIN 10 FEET OF THE EXTERIOR |
| | STAIRS. PLEASE REVIEW SECTION 2010 FBC-B 1026.6 |
| | EXTERIOR STAIRWAY AND RAMP PROTECTION. |
| | EXTERIOR EXIT STAIRWAYS AND RAMPS SHALL BE SEPARATED |
| | FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN |
| | SECTION 1022.2. OPENINGS SHALL BE LIMITED TO THOSE |
| | NECESSARY FOR EGRESS FROM NORMALLY OCCUPIED SPACES. |
| | 1) BUILDING PROVISO: DEFERRED SUBMITTAL. ELEVATOR |
| | PRODUCT DATA SHEET FOR OTIS GEN 2 ELEVATOR. |
| | |
| | FEMA TECHNICAL BULLETIN 4-93. FEMA REGULATION |
| | 60.3(A)(3) IF A PROPOSED BUILDING SITE WILL BE |
| | REASONABLY SAFE FROM FLOODING. IF A PROPOSED BUILDING |
| | SITE IS IN A FLOOD PRONE AREA, ALL NEW CONSTRUCTION AND |
| | SUBSTANTIAL IMPROVEMENTS SHALL? BE CONSTRUCTED WITH |
| | MATERIALS RESISTANT TO FLOOD DAMAGE,(III) BE |
| | CONSTRUCTED BY METHODS AND PRACTICES THAT MINIMIZE |
| | FLOOD DAMAGES, AND (IV) BE CONSTRUCTED WITH |
| | ELECTRICAL... EQUIPMENT AND OTHER SERVICES FACILITIES |
| | THAT ARE DESIGNED AND / OR LOCATED SO AS TO PREVENT |
| | WATER DAMAGE FROM ENTERING OR ACCUMULATING WITHIN THE |
| | COMPONENTS DURING CONDITIONS OF FLOODING. |
| | TO KEEP THE ELEVATOR CABS FROM HAVING SUBSTANTIAL |
| | DAMAGE FROM FLOODWATERS, IS THERE A INTERLOCKING |
| | CONTROL OR FLOAT SWITCH THAT WHEN ACTIVATED WILL KEEP |
| | THE CAB FROM DESCENDING INTO THE FLOODWATERS. |
| | |
| | 2) PROVISO: ANY EUROPEAN CAR LIFT SYSTEM WILL NEED TO |
| | SUBMIT PRODUCT LISTINGS WHERE THEY HAVE AN NRTL |
| | (NATIONALLY RECOGNIZED TESTING LABORATORY) ACCREDITED |
| | BY THE US AUTHORITY OCCUPATIONAL SAFETY AND HEALTH |
| | ADMINISTRATION AND STAMPED FOR US MARKETS. |
| | |
| | 3) BUILDING PROVISO: THE PLANS SHOW AT THE ENTRY LEVEL |
| | OF THE LOBBY A RECEPTION/ REGISTRATION DESK. PLEASE |
| | PROVIDE COMPLIANCE WITH FAIR HOUSING SPECIFICATION OF |
| | ANSI 4.31 ALSO SEE REACH RANGES. |
| | |
| | 4) BUILDING PROVISO: DEFERRED SUBMITTALS : TEST REPORTS |
| | SHOWING COMPLIANCE WITH: |
| | |
| | 4)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 4)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 4)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 5) BUILDING PROVISO: DEFERRED SUBMITTALS: SHEET |
| | 431-M4-01 MECHANICAL DETAILS EQUIPMENT SUPPORT CURB |
| | DETAIL & THYBAR VIBRATION CURB III DETAIL FOR OAU-1 & |
| | 2. PLEASE PROVIDE THE PRODUCT APPROVALS FOR CURB |
| | DETAILS. TO BE REVIEWED BY THE STRUCTURAL ENGINEER OF |
| | RECORD, AND WITH THEIR SHOP DRAWING STAMP OF APPROVAL. |
| | PLEASE NOTE THE STRUCTURAL ANCHOR TO THE BASE OR |
| | SUPPORT AS WELL AS THE UNIT TO THE CURB FOR MOMENT OF |
| | OVERTURNING, WILL NEED TO BE DESIGNED BY THE STRUCTURAL |
| | ENGINEER OR HIS DELEGATE WITH THE STRUCTURAL ENGINEERS |
| | APPROVAL BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT |
| | FOR REVIEW. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 6)BUILDING PROVISO: DEFERRED SUBMITTAL FOR |
| | ARCHITECTURAL TRIM AND EMBELLISHMENTS METAL FINS ON |
| | LEVEL 26. 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR |
| | AN ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE |
| | BUILDING OFFICIAL TO VERIFY COMPLIANCE WITH THE |
| | REQUIREMENTS OF CHAPTER 16 FOR WIND LOADS. 1407.6 |
| | WEATHER RESISTANCE. IF DELEGATED ENGINEERING THEN THE |
| | DOCUMENTS NEED TO BE FORWARDED TO THE ENGINEER OF |
| | RECORD FOR REVIEW AND APPROVAL BEFORE SUBMITTING TO THE |
| | BUILDING DEPARTMENT. 61G15-30.003. |
| | |
| | 7) BUILDING PROVISO: DEFERRED SUBMITTAL FOR THE TERRA |
| | COTTA WALL CLADDING UNITS. FOR ARCHITECTURAL TRIM AND |
| | EMBELLISHMENTS THE TERRA COTTA UNITS WILL NEED TO |
| | COMPLY WITH 2010 FBC-B 1407.5 APPROVAL. RESULTS OF |
| | APPROVED TESTS OR AN ENGINEERING ANALYSIS SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO VERIFY COMPLIANCE |
| | WITH THE REQUIREMENTS OF CHAPTER 16 FOR WIND LOADS. |
| | 1407.6 WEATHER RESISTANCE. IF DELEGATED ENGINEERING |
| | THEN THE DOCUMENTS NEED TO BE FORWARDED TO THE ENGINEER |
| | OF RECORD FOR REVIEW AND APPROVAL BEFORE SUBMITTING TO |
| | THE BUILDING DEPARTMENT. 61G15-30.003. |
| | |
| | 8) BUILDING PROVISO: DEFERRED SUBMITTAL |
| | POLYISOCYANURATE BOARD. WITH SINGLE PLY RECOVERY BOARD |
| | AND SINGLE PLY PVC ROOFING MEMBRANE ROOFING. PLEASE |
| | PROVIDE THE PRODUCT APPROVALS FOR EACH OF THE MEMBERS. |
| | FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 9)BUILDING PROVISO: DEFERRED SUBMITTALS. DETAILS 3 & 4 |
| | BOTH SHOW A TILE DECK ABOVE THE ROOFING SYSTEM. THE |
| | ROOFING SYSTEM WELL NEED TO PROVIDE PRODUCT APPROVALS |
| | FOR WIND AS WELL AS ENGINEERING FOR THE TILE DECK |
| | INSTALLATION THEY WILL MEET THE WIND LOADS FOR THE |
| | LOCATION ON THE BUILDING.2010 FBC-B COMPONENTS AND |
| | CLADDING. 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 10) BUILDING PROVISO: DEFERRED SUBMITTAL. CANOPY |
| | SYSTEMS. ADDITIONAL ENGINEERING SHEETS (SHOP DRAWINGS) |
| | TO BE SUBMITTED AS A DEFERRED SUBMITTAL. PLEASE ALSO |
| | PROVIDE HOW CODE COMPLIANCE WITH 2010 FBC-B 2405.2 |
| | ALLOWABLE GLAZING MATERIALS AND LIMITATIONS WILL BE |
| | COMPLIED WITH. FL 61G-15-30.006 (3) THE DELEGATED |
| | ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| | DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 11) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. ROOF HATCHES. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, INTAKE AND |
| | EXHAUST FANS ? |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |