Plan Review Notes
Plan Review Notes For Permit 15111020
Permit Number 15111020
Review Stop P
Sequence Number 3
Notes
Date Text
2016-12-29 13:36:003RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: FROM 1ST REVIEW HAVE NOT BEEN FULLY
 COMPLIED
  
 41.PROVIDE MANUFACTURE SPEC SHEETS FOR ALL PUMPS
 ,THERMOSTATIC MIXING VALVES, TANKS, WATER HEATERS ECT.
 PER WPB AMEND. TO FBC SEC. 107.2.1 THE DETAILLS ON THE
 PLANS ARE NOT THE MANUFACTURE SPECIFICATION THESE CAN
 BE A DEFERRED SUBMITTAL.
  
 45.SHOW CONNECTION OF IRRIGATION SYSTEM ON WATER RISER
 DIAGRAM.
 PER WPB AMEND. TO FBC SEC. 107.2.1 A BACK FLOW IS
 REQUIRED
  
 47.SHT.M4-02 NOTE ON GENERATOR DETAIL STATES THAT FUEL
 PIPPING IS TO BE DONE BY ELECTRICAL CONTRACTOR. THAT IS
 NOT IN THERE SCOPE OF REG ALLOWED BY THE STATE PLEASE
 CLARIFY. SHEET HAS NOT BEEN REVISED
  
 51.PROVIDE PROVIDE DETAILED PIPING RISER DIAGRAM FOR
 DIESEL FUEL PIPING.
 PER WPB AMEND. TO FBC SEC. 107.2.1 PROVIDE SIZE AND
 TYPE OF PIPING
  
 2ND REVIEW COMMENTS: NOT COMPLIED
  
 6. PROVIDE A NOTE FOR BACKFLOW ON POOL FILL. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 7. PLEASE PROVIDE PLUMBING FLOOR PLAN-FOR LEVEL 1 AND
 2-3 ASININITY'S WITH GRID LINES 9-17 . PER WPB AMEND.
 TO FBC SEC. 107.2.1 SHT. P2-52B IS MISSING.
  
 8. SHT. P5-28 THE HOT AND COLD WATER ISOMETRIC FOR SPA
 IS MISSING THE 2 SHOWERS IN WOMENS SPA. PER WPB AMEND.
 TO FBC SEC. 107.2.1
  
 9. SHT. P5-01+02 DOES NOT SHOW BRANCHES FOR AMENITY'S
 AND GUEST SUITES PLEASE CLARIFY. PER WPB AMEND. TO FBC
 SEC. 107.2.1
  
 12. PLEASE PROVIDE HOT AND COLD WATER ISOMETRICS FOR
 UNITS ON LEVELS 18,19, PH 20,26 PER WPB AMEND. TO FBC
 SEC. 107.2.1 A ISOMETRIC THAT IS SIMILAR DOES NOT
 COMPLY ALL FIXTURES MUST BE SHOWN!
  
 15. SHT. P5-27 ISOMETRIC FOR UNIT C IS MISSING THE
 LAUNDRY SINK. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 16. SHT. P5-01 SHOW CONNECTION FOR TRASH SHOOT WASH
 RING ON RISER. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 22. P5-23 SHOWS 12IN LINE FROM POOL DECK DRAINS SHT
 P5-04 SHOWS 8IN CLARIFY. PER WPB AMEND. TO FBC SEC.
 107.2.1
  
  
 27. SHT. P-28 SHOWS 2 SINKS NEXT TO WASHING MACHINES I
 COULD NOT FIND THEM ON THE FLOOR PLAN. PER WPB AMEND.
 TO FBC SEC. 107.2.1 SHOW ON PLUMBING FLOOR PLAN!
  
 28. P5-06 LABEL RISER AN AND INDICATE LOCATION ON FLOOR
 PLAN. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 29. P5-06 THRU 21 ISOMETRICS ARE UNCLEAR WHERE PIPES
 CONNECT SOME PIPES DO NOT CONNECT . PROVIDE A CLEAR AND
 CONCISE DRAWING SHOWING ALL PIPE SIZING AND VENT STACKS
 VS SOIL STACKS , EXPAND THE ISOMETRICS LARGER SO
 BATHROOM GROUPS DON'T RUN TOGETHER AND APPEAR TO
 CONNECT.LABEL EACH ISOMETRIC WITH LOCATION OR FLOOR
 LEVEL. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 3RD REVIEW:
  
 1. SHT. P5-03D AND 03E LABEL LOCATION OF EACH ISOMETRIC
 AND EXPAND EACH ISOMETRIC. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. A0-45 THE FLORIDA BUILDING ACCESSIBILITY CODE
 SHOULD BE 2014 5TH EDITION NOT 2012
  
 3. SHT. A0-45B THE ACCESSIBLE SHOWERS SHALL COMPLY WITH
 FBC ACC 608 IF YOUR GOING TO USE TH ALTERNATE ROLL IN
 TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES WIDE EXACT.
 THE WAY THEY ARE DESIGNED NOW IS NOT COMPLIANT.
  
 4. SHT. A0-45B THE BATHROOM IN THE WOMENS SPA THE
 CLEARANCE AROUND THE THE TOILET CAN NOT HAVE ANY THING
 ELSE IN IT THE WING WALL ON THE RIGHT SIDE OF THE
 TOILET DOES NOT COMPLY. PER FBC ACC 604.3.2
  
 5. PLEASE PROVIDE DETAILS FOR HIGHT DIMENSIONS FOR
 ACCESSIBILITY IN COMMON AREAS. PER WPB AMEND TO FBC
 107.2.1
  
 6. SHT. P5-03B S16 ON LEVEL 16 IS MISSING THE SHOWER IN
 MASTER BATHROOM BETWEEN HIS AND HERS UNIT C. PER WPB
 AMEND TO FBC 107.2.1
  
 7. SHT P5-03B S13 SHOWS A SHOWER THE FLOOR PLAN SHOWS A
 T8UB PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P2-54E-F THE WALLS AND FIXTURES DID NOT SHOW UP
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. P5- 03B S10 SHOWS DOUBLE LAVS AND A SHOWER THE
 FLOOR PLAN SHOWS A TUB AND A SINGLE LAV PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 10. SHT. P2-54C BATH 4 SHOWS ATUB S11 SHOWS A SHOWER
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 11. SHT. P5 -11 RISER TAGS MISSING PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 12. SHT. P2-54C+ B REMOVE NOTE ON KITCHEN REFERRING TO
 AAV IF A LOOP VENT IS BEING USED. PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 13. IF THE OIL SEPARATOR IS INSTALLED IN A PIT A DRAIN
 IS REQUIRED. PER WPB AMEND TO FBC 107.2.1
  
 14. SHT. P5-01 ON LEVEL 3 THE RISER FOR HW-9 SHOWS 1"
 THE DETAIL ON SHT. P5-28 SHOWS 11/2 FOR HW-9 + CW-9 .
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 15. SHT.P5-01 + 02 THE BRANCHES FOR LEVELS 1,2,3 ARE
 NOT SHOWN . PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 16. SHT. P5-27 THE RISER DETAI FOR TYP. UNIT A 5-17 IS
 MISSING BATH2 . PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 IN ORDER TO EXPEDITE THIS PERMIT I WOULD ADVISE A
 MEETING TO GO OVER COMMENT AND CLARIFY ANY ISSUES
 PLEASE CONTACT ME. [email protected] OR 561-805-6711
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
  
  
  
  
 POOL COMMENTS:
  
 1. POOL ,HOT SPA POOL , HIS AND HER JACUZZIS AND ALL
 WATER FEATURES REQUIRE SEPARATE PERMIT FROM MAIN
 BUILDING.\
 2. SHALL OBTAIN OPERATING PERMIT FROM PALM BEACH COUNTY
 HEALTH DEPARTMENT. SHOW NOTE ON PLAN
 PER FBC SEC. 454
 NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS
 APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-9,
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 514, FLORIDA
 STATUTES. THE REGULATION AND ENFORCEMENT OF THE INITIAL
 AND ANNUAL OPERATION PERMIT FOR PUBLIC POOLS ARE
 PREEMPTED TO THE DOH. THE CONSTRUCTION PERMIT HOLDER IS
 RESPONSIBLE FOR OBTAINING AN OPERATION PERMIT ISSUED BY
 DOH, AS A PUBLIC SWIMMING POOL SHALL NOT BE PUT INTO
 OPERATION WITHOUT AN INSPECTION AND OPERATION PERMIT
 ISSUED FROM THE DOH. DOH MAY GRANT VARIANCES FROM THE
 PROVISIONS OF THE FLORIDA BUILDING CODE SPECIFICALLY
 PERTAINING TO PUBLIC SWIMMING POOLS AND BATHING PLACES
 AS AUTHORIZED BY SECTION 514.0115, FLORIDA STATUTES.
 BUILDING OFFICIALS SHALL RECOGNIZE AND ENFORCE VARIANCE
 ORDERS ISSUED BY THE DEPARTMENT OF HEALTH PURSUANT TO
 SECTION 514.0115(5), FLORIDA STATUTES INCLUDING ANY
 CONDITIONS ATTACHED TO THE GRANTING OF THE VARIANCE.
  
  
 14. ONE URINAL IS REQUIRED IN MEN?S POOL BATHROOM. PER
 FBC PL TABLE 403.6 AND SEC 403.6 SHT. A2.52B DOES NOT
 SHOW URINAL IN MENS BATHROOM.
  
 18. SHOW COMPLIANCE FOR OZONE EQUIPMENT ROOM
 VENTILATION MUST COMPLY WITH FBC SEC. 545.1.6.5.16.4.5
 PLEASE PROVIDE SHT. NUMBERS
  
 24. PROVIDE MSDS SHEETS FOR ALL CHEMICALS USED. PER WPB
 AMEND. TO FBC 107.2.
  
 28. OZONE GENERATING EQUIPMENT ELECTRICAL COMPONENTS
 AND WIRING SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 27 OF THIS CODE AND THE MANUFACTURER SHALL
 PROVIDE A CERTIFICATE OF CONFORMANCE. THE PROCESS
 EQUIPMENT SHALL BE PROVIDED WITH AN EFFECTIVE MEANS TO
 ALERT THE USER WHEN A COMPONENT OF THIS EQUIPMENT IS
 NOT OPERATING PER FBC 454.1.6.5.16.4.1 SHOW NOTE ON
 PLAN
  
 29. PROVIDE SPECS FOR CHANNEL DRAINS FOR SPAL. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 NEW COMMENTS
  
 1. FOR THE TRANSFER WALL AT HOT SPA SHOW COMPLIANCE
 WITH FBC ACC (A) 1009.4.1 CLEAR DECK SPACE.
 A CLEAR DECK SPACE OF 60 INCHES (1525 MM) MINIMUM BY 60
 INCHES (1525 MM) MINIMUM WITH A SLOPE NOT STEEPER THAN
 1:48 SHALL BE PROVIDED AT THE BASE OF THE TRANSFER
 WALL. WHERE ONE GRAB BAR IS PROVIDED, THE CLEAR DECK
 SPACE SHALL BE CENTERED ON THE GRAB BAR. WHERE TWO GRAB
 BARS ARE PROVIDED, THE CLEAR DECK SPACE SHALL BE
 CENTERED ON THE CLEARANCE BETWEEN THE GRAB BARS.
 (B)1009.4.2 HEIGHT.
 THE HEIGHT OF THE TRANSFER WALL SHALL BE 16 INCHES (405
 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM MEASURED
 FROM THE DECK.
 (C)1009.4.5 GRAB BARS.
 AT LEAST ONE GRAB BAR COMPLYING WITH 609 SHALL BE
 PROVIDED ON THE TRANSFER WALL. GRAB BARS SHALL BE
 PERPENDICULAR TO THE POOL WALL AND SHALL EXTEND THE
 FULL DEPTH OF THE TRANSFER WALL. THE TOP OF THE
 GRIPPING SURFACE SHALL BE 4 INCHES (100 MM) MINIMUM AND
 6 INCHES (150 MM) MAXIMUM ABOVE TRANSFER WALLS. WHERE
 ONE GRAB BAR IS PROVIDED, CLEARANCE SHALL BE 24 INCHES
 (610 MM) MINIMUM ON BOTH SIDES OF THE GRAB BAR. WHERE
 TWO GRAB BARS ARE PROVIDED, CLEARANCE BETWEEN GRAB BARS
 SHALL BE 24 INCHES (610 MM) MINIMUM.
  
 2. DETAILS NOT SHOWN FOR BACKFLOW /AIR GAP ON FILL
 LINES AND OVER FLOW FILL LINE BOX FOR WATER FEATURE.
 PER WPB AMEND TO FBC 107.2.1
  
 3. THE CRYSTAL FOUNTAIN SHOWS AN OVERFLOW CONNECTING TO
 A SEWER YOU SHALL RECEIVE APPROVAL FROM ENGINEERING
 DEPARTMENT TO CONNECT ANY OVERFLOW FROM WATER FEATURES
 OR POOL EQUIPMENT CONTACT MANUEL GONZALEZ 561-494-1085
  
  
  
  
  
  
  
 DO TO THE DEFICIENCY'S AND SOME SHEETS BEING UNCLEAR A
 COMPLETE AND COMPREHENSIVE REVIEW OF THE PLUMBING
 SYSTEMS CAN NOT BE COMPLETED AT THIS TIME. THIS MAY
 GENERATE MORE COMMENTS UPON SECOND REVIEW.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  