| 2016-12-21 17:48:24 | 3RD REVIEW FBC-2014 MECHANICAL |
| | PERMIT #15111020 |
| | 12/20/16 |
| | |
| | 1) ALL SUBMITTED ENGINEERED MECHANICAL PLANS, |
| | DOCUMENTS, AND CALCULATIONS SHALL BEAR THE ELECTRONIC |
| | SEAL AND SIGNATURE OF THE ENGINEER OF RECORD- SECTION |
| | 471.025 F.S. AND SECTION 61G15-23.005 FLORIDA |
| | ADMINISTRATIVE CODE. CURRENTLY NONE OF THE UPLOADED |
| | PLANS, DOCUMENTS, OR CALCULATIONS ARE IN COMPLIANCE. |
| | |
| | 2) THE FOLLOWING SHEETS DO NOT BEAR THE TITLE BLOCK OF |
| | THE APPARENT ENGINEER OF RECORD- EDWARDS & ZUCK: SHEETS |
| | M2.54E, M2.54F, M4.01- M4.05, & M5.01- M5.03, & M6.01. |
| | |
| | 3) 3RD REQUEST FOR THE ENERGYGAUGE SUBMITTAL TO BE |
| | CORRECTED TO MATCH THE EQUIPMENT SCHEDULES- 3RD REQUEST |
| | TO COMPLY. REFER BACK TO 1ST REVIEW COMMENT #1 |
| | |
| | 4) 3RD REQUEST FOR AC COOLING AND HEATING CALCULATIONS. |
| | REFER BACK TO 1ST REVIEW COMMENT #2 |
| | |
| | 5) SHEET M2.0P1 & M2.0P2: PLACE A NOTE ON THE PLANS |
| | REFERENCING SHEET M5-07 FOR CONTROLS OPERATIONS FOR THE |
| | GARAGE EXHAUST FANS. REVISE THE NOTES ON M5-07 TO SHOW |
| | A CONTINUOUS MINIMUM EXHAUST RATE OF .05 CFM PER |
| | SQ.FT.- SECTION 404.2 |
| | |
| | 6) M2.0P1 & M6.02: THE NOTES IN THE FAN SCHEDULE |
| | INDICATE THE GARAGE EXHAUST FANS ARE NOT HIGH WIND |
| | RATED. |
| | |
| | 7) M2.0P2 & M6.02: PGEF-P2- 1C & 1D LISTED IN THE |
| | EXHAUST CALCULATIONS ARE NOT IN THE SCHEDULE. |
| | PGEF-P2-1A & 1B DO NOT HAVE LARGE ENOUGH CAPACITY TO |
| | EXHAUST THE REQUIRED 38,790 CFMS OF EXHAUST. |
| | |
| | 8) M2.01: VERIFY WITH NOTES ON MEASUREMENTS THE |
| | SEPARATION DISTANCES BETWEEN THE GENERATOR AND TANK |
| | ROOM EXHAUST OUTLETS AND THE GENERATOR ROOM AIR INTAKE |
| | LOUVER. THE ELEVATION DRAWING APPEARS TO INDICATE |
| | NON-COMPLIANCE- SEE SHEET A3.35. |
| | |
| | 9) M2.01: IT APPEARS THAT THE DRYER AND IRONER EXHAUST |
| | DUCTS ARE RUNNING THROUGH AN ABOVE CEILING PLENUM WHICH |
| | IS PROHIBITED PER SECTION 504.4. PLEASE CLEARLY |
| | DESIGNATE THE LOCATIONS OF ABOVE CEILING PLENUMS. |
| | |
| | 10) M2.01: IT APPEARS MOTORIZED DAMPERS ARE MISSING FOR |
| | THE O/A SUPPLY TO THE GUESTROOMS. |
| | |
| | 11) M5.04 & M6.02: REFER TO THE SUMMARY TABLE ON PAGE |
| | 26 OF THE SMOKE CONTROL RATIONAL ANALYSIS. THE |
| | LOCATIONS OF THE STAIRWELL PRESSURIZATIONS FANS AND FAN |
| | CAPACITIES SPECIFIED IN THE UPDATED REPORT DIFFER FROM |
| | THE SPECIFICATIONS IN THE DRAWINGS AND THE SCHEDULE. A) |
| | THE NOTES IN THE SCHEDULE INDICATE THE STAIRWELL AND |
| | ELEVATOR PRESSURIZATION FANS ARE NOT HIGH-WIND RATED, |
| | AND NOT UL LISTED FOR SMOKE CONTROL. |
| | |
| | 12) M5.04: ALL OF THE PRINTED NOTES AND LABELS ON THE |
| | PLAN ARE BARELY LEGIBLE AND NEED TO BE EMBOLDENED. THE |
| | LETTERS "N.C." ARE SHOWN AT EACH HORIZONTAL SHAFT |
| | OPENING. PLEASE CLARIFY WHAT THOSE LETTERS STAND FOR. |
| | |
| | 13) M6.02 FAN SCHEDULE: THE NOTES IN THE REMARKS COLUMN |
| | ARE CONFUSING FOR THE TEF'S AND THE KEF'S. SOME OF THE |
| | TEF'S ON THE ROOF HAVE NOAS AND SOME DON'T. AND HOW CAN |
| | A TEF AND A KEF HAVE THE SAME NOA NUMBER? PLEASE NOTE |
| | NOA#14-0325-06 LISTED IN THE NOTES WAS NOT FOUND ON THE |
| | MIAMI-DADE PRODUCT CONTROL WEBSITE. |
| | |
| | 14) A5.28: THE GARAGE EXHAUST FAN OUTLETS CANNOT BE |
| | LOCATED OVER STAIRWELL #9 PLATFORM AND STAIRS- SEE |
| | SECTIONS 501.3, 501.3.1(10) & 501.3.1.1. |
| | |
| | 15) M5.05 & M5.06: PLEASE CIRCLE OR HIGHLIGHT THE |
| | LOCATION OF OAU-3 IN THE CONDENSER WATER RISER DRAWING. |
| | |
| | 16) M2.01: IN REFERENCE TO COMMENT #28 FROM THE 2ND |
| | REVIEW, THE PLAN STILL APPEARS TO INDICATE HP-1L-5 AND |
| | HP-1L-6 ARE SHARING A COMMON PLENUM WHICH WOULD REQUIRE |
| | A SMOKE DETECTOR. I AM NOT SEEING A DUCTED RETURN FROM |
| | THE CONFERENCE ROOM AS STATED IN THE NARRATIVE. |
| | |
| | 17) M2.01: COMMENT #29 FROM THE 2ND REVIEW STILL |
| | EXISTS: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | DRYERS AND IRONER- SEE SECTION 304 FBC-14 FUEL GAS. A) |
| | SEE PREVIOUS COMMENT #9. |
| | |
| | 18) M2.01: PROVIDE AIR BALANCE CALCULATIONS FOR THE |
| | LAUNDRY AND MANICURE ROOMS. |
| | |
| | 19) M2.01: TELECOM HP NOT LABELED AS REQUESTED. |
| | |
| | 20) M2.01: COMMENT #35 FROM THE 2ND REVIEW STILL |
| | EXISTS- PLEASE COMPLY. |
| | |
| | 21) M2.01: DEMAND CONTROLLED VENTILATION IS REQUIRED |
| | FOR THE CLUB DINING ROOM- SECTION 503.2.1 FBC-10 ENERGY |
| | CONSERVATION. INDICATE A MEANS ON THE PLANS. |
| | |
| | 22) M2.02: AS PREVIOUSLY REQUESTED LABEL THE EXHAUST |
| | FANS IN THE WOMEN'S AMENITY AREA. |
| | |
| | 23) M2.02: PLEASE CLEARLY DESIGNATE ON THE PLAN THE |
| | LOCATIONS OF ALL ABOVE CEILING PLENUM SPACES. |
| | |
| | 24) M2.02 & A6.87: REFER TO SECTION 602.2 & 606.2.1 AND |
| | VERIFY THE LIGHT COVES BEING USED AS RETURN GRILLS ARE |
| | IN COMPLIANCE. |
| | |
| | 25) M2.03 AND ALL OTHER PLAN SHEETS SHOWING CHILLED |
| | WATER PIPING: IDENTIFY ALL HP UNITS BEING SERVICED BY |
| | THE PIPING ON EACH FLOOR. |
| | |
| | 26) M2.23: THE DUCTWORK IS NOT SHOWN IN THE NORTH CORE. |
| | |
| | 27) M2.5B: PROVIDE A NOTE OR DETAIL SHOWING THE 2HR. |
| | RATED SOFFIT ENCLOSING THE RETURN DUCT IN THE NORTH |
| | STAIR TOWER, AND PROVIDE FS DAMPERS AT RATED WALL |
| | PENETRATIONS. |
| | |
| | 28) BASED ON THE RESPPONSES TO THE COMMENTS THERE WILL |
| | BE MANY DEFERRED SUBMITTALS FOR THE PROPOSED PROJECT. |
| | PLESASE REVIEW THE FOLLWOING SECTIONS FROM THE WPB |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE. |
| | |
| | 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | 2) DEFERRED SUBMITTAL. 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | THE CURRENT LIST OF DEFERRED SUBMITTALS BASED ON |
| | COMMENT RESPONSES ARE: |
| | A) STRUCTURAL DETAILS AND WIND LOAD ENGINEERING FOR ALL |
| | ROOFTOP AND EXTERIOR MECHANICAL EQUIPMENT AND |
| | COMPONENTS INCLUDUNG THE COOLING TOWER, THE DOA UNITS, |
| | THE FANS AND FAN CURBS, LOUVERS, ETC. |
| | B) STRUCTURAL DRAWINGS AND DETAILS FOR THE COOLING |
| | TOWER ACCESS PLATFORM AND LADDER. |
| | C) MANUFACTURER'S SPECIFICATIONS FOR THE COOLING TOWER, |
| | CHILLED WATER PIPING INSULATION, SMOKE CONTROL AND |
| | PRESSURIZATION FANS, BOILER AND BOILER VENTING, THE |
| | HEAT EXHANGERS, FLAMEBAR DUCT, FS DAMPERS, O/A |
| | MOTORIZED DAMPERS, CO DETECTORS, AND FIRESTOPPING |
| | SEALERS AND CAULKS. |
| | D) ACCESS PANELS FOR ABOVE CEILNG HP'S |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |