| Plan Review Notes For Permit 15111020 |
| Permit Number |
15111020 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-12-28 16:30:32 | | | | | | | 2ND REVIEW: FBC 2010 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS:3RD REQUEST | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR EACH | | | APPLIANCE WITH CUBIC FT. REQUIRED AND WHAT IS PROVIDED | | | PER THE FBC-2010 FUEL GAS CODE SEC. 304. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 3RD REVIEW: | | | | | | 1. BTU LOADS ON THE GAS RISER ARE SHOWN AS CFH SHOULD | | | THEY BE MBH OR BTU PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 2. UNDER THE GAS CALCULATIONS THE TOTAL GAS | | | CONSUMMATION IS SHOWN AS CFH PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 3.TABLE LISTED FOR SIZING IS FOR LESS THAN 2PSI WITH A | | | PRESSURE DROP OF 0.6 IN. THE MAIN SYSTEM IS SHOWN AS | | | 2PSI PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 4. PLEASE PROVIDE A RISER DIAGRAM FOR UNIT SHOWING | | | LOCATION IF THE UNITS. PER WPB AMEND TO FBC 107.2.1 | | | | | | IN ORDER TO EXPEDITE ISSUANCE OF THIS PERMIT I SUGGEST | | | THE WE SET UP A MEETING PLEASE CONTACT ME CONTACT INFO | | | I | | | | | | | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | | | | |
|