| Date |
Text |
| 2016-08-11 08:55:42 | 2ND REVIEW |
| | |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: FROM 1ST REVIEW HAVE NOT BEEN FULLY |
| | COMPLIED |
| | |
| | 1. SHT. A6-70F DETAIL 3 IS CALLING OUT BATH 2 FOR SPEC |
| | B FHA, DETAIL 2 IS CALLING OUT BATH 2 AS STANDARD ,IT |
| | APPEARS TO BE A TYPO PLEASE CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 2. SHOLL WHICH BATHROOM IS DESIGNATED FOR FHA UNIT |
| | 21A-21B. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | |
| | 5. SHOW ACCESSIBILITY LEVEL FOR AMENITY BATH ROOMS ON |
| | LEVEL 1-3. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 11. SHT. P5-01 SHOWS 6IN. CW RISER RUNNING UP FROM |
| | PUMPS TO BLADDER TANKS WHERE DOES IT CONNECT WITH THE |
| | REST OF THE WATER RISER PLEASE CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 14.INDICATE DIRECTION OF FLOW MORE CLEARLY ON HOT WATER |
| | RECIRCULATION SYSTEM. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 16.SHT. P5-13 SHOWS S-13A NOT SHOWN ON P5-05 PLEASE |
| | CLARIFY. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | |
| | 31. SHT.P2-01 DD-2 BETWEEN LINES 1-2 AND A-D IS MISSING |
| | ON RISER DIAGRAM ON SHT. P5-24 ALSO MISSING PD BETWEEN |
| | LINES 1-2 A-D. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 34.SHT. C3-01 SHOWS EXISTING SEWER TO BE USED AS DRAIN |
| | FOR FOUNTAIN. WATER FROM FOUNTAIN POOLS AND WATER |
| | FEATURES SHALL NOT DRAIN INTO SANITARY PER. WPB ORD. |
| | SEC. 90-126.(5) |
| | 35. PROVIDE CALCULATIONS FOR STORM SUMP PUMP AND OIL |
| | SAND SEPARATORS. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 36. SHT. P5-24 SHORT TRENCH DRAINS MISSING SQ FT CALC . |
| | PLEASE PROVIDE. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 39. PROVIDE MANUFACTURE SECS FOR OIL SAND SEPARATOR. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 41.PROVIDE MANUFACTURE SPEC SHEETS FOR ALL PUMPS |
| | ,THERMOSTATIC MIXING VALVES, TANKS, WATER HEATERS ECT. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 45.SHOW CONNECTION OF IRRIGATION SYSTEM ON WATER RISER |
| | DIAGRAM. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 46. SEPARATE PERMITS REQUIRED FOR BACKFLOW PREVENTER'S |
| | AT METERS. FOR IRRIGATION, DOMESTIC, AND COOLING TOWERS |
| | POOL FILL,FIRE |
| | 47.SHT.M4-02 NOTE ON GENERATOR DETAIL STATES THAT FUEL |
| | PIPPING IS TO BE DONE BY ELECTRICAL CONTRACTOR. THAT IS |
| | NOT IN THERE SCOPE OF REG ALLOWED BY THE STATE PLEASE |
| | CLARIFY. |
| | |
| | 51.PROVIDE PROVIDE DETAILED PIPING RISER DIAGRAM FOR |
| | DIESEL FUEL PIPING. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | 52. WHERE DOES THE SUMP DRAINS ON FUEL PUMPS DISCHARGE |
| | TO. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | IN YOUR RESPONSE LETTER MANY OF YOUR NARRATIVES JUST |
| | SAY REFER TO REVISED SHEET THIS DOES NOT GIVE ME MUCH |
| | INFORMATION. IF YOU COULD REFERENCE A SPECIFIC SHEET IT |
| | WOULD GREATLY EXPEDITE MY PLAN REVIEW PROCESS AND BE |
| | GREATLY APPRECIATED THANK YOU. |
| | |
| | |
| | 2ND REVIEW COMMENTS: |
| | |
| | 1. IN REFERENCE TO PREVIOUS COMMENT #5 PLEASE PROVIDE |
| | DETAILS SHOWING COMPLIANCE WITH TH E FBC ACC. SHOW ALL |
| | THE HEIGHTS OF GRAB BARS, TOILET SEATS, LAVATORY'S, |
| | MIRRORS, TOILET PAPER DISPENSERS, SHOWER CONTROL |
| | LOCATIONS AND SHOWER SEATS, DRINKING FOUNTAIN SHOW |
| | CLEAR FLOOR SPACE FOR ALL FIXTURES. PER WPB AMEND. TO |
| | FBC SEC. 107.2.1 |
| | |
| | 2. SHT. A2-52A SHOW INSIDE DIMENSIONS OF BATHROOMS |
| | 207-205. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 3. BATHROOMS NEXT TO JACUZZI IN MENS AND WOMENS SPA |
| | SHALL BE ACCESSIBLE.PER FBC ACC. 213.2 |
| | |
| | 4. USING YOUR OCCUPANT TYPE AND LOAD FROM SHT. A0-32 I |
| | HAVE DETERMINED THAT ON THE 1ST LEVEL ( LOBBY) IT IS |
| | REQUIRED TO HAVE 4 WATER CLOSETS FOR THE MEN AND 4 FOR |
| | THE WOMEN 6 LAVS 2 DRINKING FOUNTAINS AND 1 SERVICE |
| | SINK . IT APPEARS THAT YOU ARE SHORT 3 WATER CLOSETS 5 |
| | LAVS PER SEX AND 2 DRINKING FOUNTAIN AND 1 SERVICE |
| | SINK. PER FBC PL TABLE 403.1 |
| | |
| | 5. 4. USING YOUR OCCUPANT TYPE AND LOAD FROM SHT. A0-33 |
| | I HAVE DETERMINED THAT ON THE 2ND LEVEL (AMENITY'S) IT |
| | IS REQUIRED TO HAVE 3 WATER CLOSETS FOR THE MEN AND 4 |
| | FOR THE WOMEN 2 LAVS PER SEX 2 DRINKING FOUNTAINS AND 1 |
| | SERVICE SINK . IT APPEARS THAT YOU ARE SHORT 1 WATER |
| | CLOSET-FOR THE WOMEN 2 DRINKING FOUNTAIN AND 1 SERVICE |
| | SINK. PER FBC PL TABLE 403.1 |
| | |
| | 6. PROVIDE A NOTE FOR BACKFLOW ON POOL FILL. PER WPB |
| | AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 7. PLEASE PROVIDE PLUMBING FLOOR PLAN-FOR LEVEL 1 AND |
| | 2-3 ASININITY'S WITH GRID LINES 9-17 . PER WPB AMEND. |
| | TO FBC SEC. 107.2.1 |
| | |
| | 8. SHT. P5-28 THE HOT AND COLD WATER ISOMETRIC FOR SPA |
| | IS MISSING THE 2 SHOWERS IN WOMENS SPA. PER WPB AMEND. |
| | TO FBC SEC. 107.2.1 |
| | |
| | 9. SHT. P5-01+02 DOES NOT SHOW BRANCHES FOR AMENITY'S |
| | AND GUEST SUITES PLEASE CLARIFY. PER WPB AMEND. TO FBC |
| | SEC. 107.2.1 |
| | |
| | 10. SHT. P5-27 ISOMETRICS FOR UNITS 3,7,11 ARE MISSING |
| | THE WATER CLOSET AND LAVATORY'S. PER WPB AMEND. TO FBC |
| | SEC. 107.2.1 |
| | |
| | 11. SHT. P5-27 THE PIPE SIZING IS TO LITE TO BE EASILY |
| | READ PLEASE CHECK ALL SHEETS AND CORRECT. PER WPB |
| | AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 12. PLEASE PROVIDE HOT AND COLD WATER ISOMETRICS FOR |
| | UNITS ON LEVELS 18,19, PH 20,26 PER WPB AMEND. TO FBC |
| | SEC. 107.2.1 |
| | |
| | 13. SHT. P5-27 ISOMETRIC FOR UNIT A IS MISSING THE TUB |
| | IN THE BATHROOM AT GRID LINES S+6 ON SHT. P2-54C. PER |
| | WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 13 SHT P5-27 THE ISOMETRIC FOR UNIT B IS MISSING THE |
| | LAV IN THE BATHROOM AT GRID LINES P-8.5 ON SHT P2-54C. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 14. SHT.P5-27 THE BATHROOM ON GRID LINES P.5-6 ON SHT |
| | P2-54C IS SHOWN AS A SHOWER ON THE ISOMETRIC AND A TUB |
| | ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND. TO FBC |
| | SEC. 107.2.1 |
| | |
| | 15. SHT. P5-27 ISOMETRIC FOR UNIT C IS MISSING THE |
| | LAUNDRY SINK. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 16. SHT. P5-01 SHOW CONNECTION FOR TRASH SHOOT WASH |
| | RING ON RISER. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 17. SHT. P5-01 AT THE MECHANICAL LEVEL IT SHOWS THE 4IN |
| | AND 6IN CW CONNECTING TOGETHER CONNECTING TWICE PROVIDE |
| | A RISER THAT CLEARLY SHOWS WHERE PIPES CONNECT AND |
| | WHERE THEY CROSS. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 18. UNABLE TO LOCATE SANITARY RISER FROM LEVEL 16 DOWN. |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 19. SHT P5-06 LABEL STACKS AND INDICATE ON THE DRAWING |
| | FLOOR LEVEL . PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 20. SHT P5-03-10 FIXTURE LAYOUT AND PIPE SIZING DO NOT |
| | MATCHISOMETRCS ON P5-10 THEYE UNCLEAR AND DON'T SEAM TO |
| | BE COMPLETE SOME OF THE BRANCHES SEAM TO CONNECT AT TWO |
| | DIFFERENT STACKS SOME STACKS DON'T CONNECT ANY WHERE. |
| | PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 21. PLEASE LABEL STORM RISERS ON THE ISOMETRIC DRAWINGS |
| | PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 22. P5-23 SHOWS 12IN LINE FROM POOL DECK DRAINS SHT |
| | P5-04 SHOWS 8IN CLARIFY. PER WPB AMEND. TO FBC SEC. |
| | 107.2.1 |
| | |
| | 23. SHT- 23 DETAIL #2 I WAS UNABLE TO LOCATE THESE |
| | DRAINS ON FOR PLANS LABEL WITH LOCATION. PER WPB AMEND. |
| | TO FBC SEC. 107.2.1 |
| | |
| | 24. SHT P5-04 PROVIDE SQFT ON RISERS. PER WPB AMEND. TO |
| | FBC SEC. 107.2.1 |
| | |
| | 25. SHT. P5-21 INDICATE ON PLAN AT WHAT PITCH THE |
| | PIPING WILL BE INSTALLED AND-SHOW SQFT ON EACH SECTION |
| | OF PIPE. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 26. SHT. P5-21 THE ISOMETRIC FOR RD 11,19,20,21IT IS |
| | UNCLEAR HOW OR WHERE TO THE RISERS. PER WPB AMEND. TO |
| | FBC SEC. 107.2 |
| | |
| | 27. SHT. P-28 SHOWS 2 SINKS NEXT TO WASHING MACHINES I |
| | COULD NOT FIND THEM ON THE FLOOR PLAN. PER WPB AMEND. |
| | TO FBC SEC. 107.2.1 |
| | |
| | 28. P5-06 LABEL RISER AN AND INDICATE LOCATION ON FLOOR |
| | PLAN. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 29. P5-07THRU21 ISOMETRICS ARE UNCLEAR WHERE PIPES |
| | CONNECT SOME PIPES DO NOT CONNECT . PROVIDE A CLEAR AND |
| | CONCISE DRAWING SHOWING ALL PIPE SIZING AND VENT STACKS |
| | VS SOIL STACKS , YOU MAY HAVE TO EXPAND THE ISOMETRICS |
| | LARGER SO BATHROOM GROUPS DON'T RUN TOGETHER AND APPEAR |
| | TO CONNECT. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | |
| | IN YOUR RESPONSE LETTER MANY OF YOUR NARRATIVES JUST |
| | SAY REFER TO REVISED SHEET THIS DOES NOT GIVE ME MUCH |
| | INFORMATION. IF YOU COULD REFERENCE A SPECIFIC SHEET IT |
| | WOULD GREATLY EXPEDITE MY PLAN REVIEW PROCESS AND BE |
| | GREATLY APPRECIATED THANK YOU. |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | POOL COMMENTS: |
| | |
| | 1. POOL ,HOT SPA POOL , HIS AND HER JACUZZIS AND ALL |
| | WATER FEATURES REQUIRE SEPARATE PERMIT FROM MAIN |
| | BUILDING.\ |
| | 2. SHALL OBTAIN OPERATING PERMIT FROM PALM BEACH COUNTY |
| | HEALTH DEPARTMENT. SHOW NOTE ON PLAN |
| | PER FBC SEC. 454 |
| | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS |
| | APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-9, |
| | FLORIDA ADMINISTRATIVE CODE AND CHAPTER 514, FLORIDA |
| | STATUTES. THE REGULATION AND ENFORCEMENT OF THE INITIAL |
| | AND ANNUAL OPERATION PERMIT FOR PUBLIC POOLS ARE |
| | PREEMPTED TO THE DOH. THE CONSTRUCTION PERMIT HOLDER IS |
| | RESPONSIBLE FOR OBTAINING AN OPERATION PERMIT ISSUED BY |
| | DOH, AS A PUBLIC SWIMMING POOL SHALL NOT BE PUT INTO |
| | OPERATION WITHOUT AN INSPECTION AND OPERATION PERMIT |
| | ISSUED FROM THE DOH. DOH MAY GRANT VARIANCES FROM THE |
| | PROVISIONS OF THE FLORIDA BUILDING CODE SPECIFICALLY |
| | PERTAINING TO PUBLIC SWIMMING POOLS AND BATHING PLACES |
| | AS AUTHORIZED BY SECTION 514.0115, FLORIDA STATUTES. |
| | BUILDING OFFICIALS SHALL RECOGNIZE AND ENFORCE VARIANCE |
| | ORDERS ISSUED BY THE DEPARTMENT OF HEALTH PURSUANT TO |
| | SECTION 514.0115(5), FLORIDA STATUTES INCLUDING ANY |
| | CONDITIONS ATTACHED TO THE GRANTING OF THE VARIANCE. |
| | |
| | |
| | 14. ONE URINAL IS REQUIRED IN MEN?S POOL BATHROOM. PER |
| | FBC PL TABLE 403.6 AND SEC 403.6 SHT. A2.52B DOES NOT |
| | SHOW URINAL IN MENS BATHROOM. |
| | |
| | 18. SHOW COMPLIANCE FOR OZONE EQUIPMENT ROOM |
| | VENTILATION MUST COMPLY WITH FBC SEC. 545.1.6.5.16.4.5 |
| | PLEASE PROVIDE SHT. NUMBERS |
| | |
| | 24. PROVIDE MSDS SHEETS FOR ALL CHEMICALS USED. PER WPB |
| | AMEND. TO FBC 107.2. |
| | |
| | 28. OZONE GENERATING EQUIPMENT ELECTRICAL COMPONENTS |
| | AND WIRING SHALL COMPLY WITH THE REQUIREMENTS OF |
| | CHAPTER 27 OF THIS CODE AND THE MANUFACTURER SHALL |
| | PROVIDE A CERTIFICATE OF CONFORMANCE. THE PROCESS |
| | EQUIPMENT SHALL BE PROVIDED WITH AN EFFECTIVE MEANS TO |
| | ALERT THE USER WHEN A COMPONENT OF THIS EQUIPMENT IS |
| | NOT OPERATING PER FBC 454.1.6.5.16.4.1 SHOW NOTE ON |
| | PLAN |
| | |
| | 29. PROVIDE SPECS FOR CHANNEL DRAINS FOR SPAL. PER WPB |
| | AMEND. TO FBC SEC. 107.2.1 |
| | |
| | NEW COMMENTS |
| | |
| | 1. FOR THE TRANSFER WALL AT HOT SPA SHOW COMPLIANCE |
| | WITH FBC ACC (A) 1009.4.1 CLEAR DECK SPACE. |
| | A CLEAR DECK SPACE OF 60 INCHES (1525 MM) MINIMUM BY 60 |
| | INCHES (1525 MM) MINIMUM WITH A SLOPE NOT STEEPER THAN |
| | 1:48 SHALL BE PROVIDED AT THE BASE OF THE TRANSFER |
| | WALL. WHERE ONE GRAB BAR IS PROVIDED, THE CLEAR DECK |
| | SPACE SHALL BE CENTERED ON THE GRAB BAR. WHERE TWO GRAB |
| | BARS ARE PROVIDED, THE CLEAR DECK SPACE SHALL BE |
| | CENTERED ON THE CLEARANCE BETWEEN THE GRAB BARS. |
| | (B)1009.4.2 HEIGHT. |
| | THE HEIGHT OF THE TRANSFER WALL SHALL BE 16 INCHES (405 |
| | MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM MEASURED |
| | FROM THE DECK. |
| | (C)1009.4.5 GRAB BARS. |
| | AT LEAST ONE GRAB BAR COMPLYING WITH 609 SHALL BE |
| | PROVIDED ON THE TRANSFER WALL. GRAB BARS SHALL BE |
| | PERPENDICULAR TO THE POOL WALL AND SHALL EXTEND THE |
| | FULL DEPTH OF THE TRANSFER WALL. THE TOP OF THE |
| | GRIPPING SURFACE SHALL BE 4 INCHES (100 MM) MINIMUM AND |
| | 6 INCHES (150 MM) MAXIMUM ABOVE TRANSFER WALLS. WHERE |
| | ONE GRAB BAR IS PROVIDED, CLEARANCE SHALL BE 24 INCHES |
| | (610 MM) MINIMUM ON BOTH SIDES OF THE GRAB BAR. WHERE |
| | TWO GRAB BARS ARE PROVIDED, CLEARANCE BETWEEN GRAB BARS |
| | SHALL BE 24 INCHES (610 MM) MINIMUM. |
| | |
| | 2. DETAILS NOT SHOWN FOR BACKFLOW /AIR GAP ON FILL |
| | LINES AND OVER FLOW FILL LINE BOX FOR WATER FEATURE. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. THE CRYSTAL FOUNTAIN SHOWS AN OVERFLOW CONNECTING TO |
| | A SEWER YOU SHALL RECEIVE APPROVAL FROM ENGINEERING |
| | DEPARTMENT TO CONNECT ANY OVERFLOW FROM WATER FEATURES |
| | OR POOL EQUIPMENT CONTACT MANUEL GONZALEZ 561-494-1085 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | DO TO THE DEFICIENCY'S AND SOME SHEETS BEING UNCLEAR A |
| | COMPLETE AND COMPREHENSIVE REVIEW OF THE PLUMBING |
| | SYSTEMS CAN NOT BE COMPLETED AT THIS TIME. THIS MAY |
| | GENERATE MORE COMMENTS UPON SECOND REVIEW. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |