Plan Review Notes
Plan Review Notes For Permit 15111020
Permit Number 15111020
Review Stop P
Sequence Number 2
Notes
Date Text
2016-08-11 08:55:422ND REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: FROM 1ST REVIEW HAVE NOT BEEN FULLY
 COMPLIED
  
 1. SHT. A6-70F DETAIL 3 IS CALLING OUT BATH 2 FOR SPEC
 B FHA, DETAIL 2 IS CALLING OUT BATH 2 AS STANDARD ,IT
 APPEARS TO BE A TYPO PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC. 107.2.1
 2. SHOLL WHICH BATHROOM IS DESIGNATED FOR FHA UNIT
 21A-21B.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
  
 5. SHOW ACCESSIBILITY LEVEL FOR AMENITY BATH ROOMS ON
 LEVEL 1-3.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 11. SHT. P5-01 SHOWS 6IN. CW RISER RUNNING UP FROM
 PUMPS TO BLADDER TANKS WHERE DOES IT CONNECT WITH THE
 REST OF THE WATER RISER PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 14.INDICATE DIRECTION OF FLOW MORE CLEARLY ON HOT WATER
 RECIRCULATION SYSTEM.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 16.SHT. P5-13 SHOWS S-13A NOT SHOWN ON P5-05 PLEASE
 CLARIFY.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
  
 31. SHT.P2-01 DD-2 BETWEEN LINES 1-2 AND A-D IS MISSING
 ON RISER DIAGRAM ON SHT. P5-24 ALSO MISSING PD BETWEEN
 LINES 1-2 A-D.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 34.SHT. C3-01 SHOWS EXISTING SEWER TO BE USED AS DRAIN
 FOR FOUNTAIN. WATER FROM FOUNTAIN POOLS AND WATER
 FEATURES SHALL NOT DRAIN INTO SANITARY PER. WPB ORD.
 SEC. 90-126.(5)
 35. PROVIDE CALCULATIONS FOR STORM SUMP PUMP AND OIL
 SAND SEPARATORS.
 PER WPB AMEND. TO FBC SEC. 107.2.1
 36. SHT. P5-24 SHORT TRENCH DRAINS MISSING SQ FT CALC .
 PLEASE PROVIDE.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 39. PROVIDE MANUFACTURE SECS FOR OIL SAND SEPARATOR.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 41.PROVIDE MANUFACTURE SPEC SHEETS FOR ALL PUMPS
 ,THERMOSTATIC MIXING VALVES, TANKS, WATER HEATERS ECT.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 45.SHOW CONNECTION OF IRRIGATION SYSTEM ON WATER RISER
 DIAGRAM.
 PER WPB AMEND. TO FBC SEC. 107.2.1
 46. SEPARATE PERMITS REQUIRED FOR BACKFLOW PREVENTER'S
 AT METERS. FOR IRRIGATION, DOMESTIC, AND COOLING TOWERS
 POOL FILL,FIRE
 47.SHT.M4-02 NOTE ON GENERATOR DETAIL STATES THAT FUEL
 PIPPING IS TO BE DONE BY ELECTRICAL CONTRACTOR. THAT IS
 NOT IN THERE SCOPE OF REG ALLOWED BY THE STATE PLEASE
 CLARIFY.
  
 51.PROVIDE PROVIDE DETAILED PIPING RISER DIAGRAM FOR
 DIESEL FUEL PIPING.
 PER WPB AMEND. TO FBC SEC. 107.2.1
 52. WHERE DOES THE SUMP DRAINS ON FUEL PUMPS DISCHARGE
 TO.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 IN YOUR RESPONSE LETTER MANY OF YOUR NARRATIVES JUST
 SAY REFER TO REVISED SHEET THIS DOES NOT GIVE ME MUCH
 INFORMATION. IF YOU COULD REFERENCE A SPECIFIC SHEET IT
 WOULD GREATLY EXPEDITE MY PLAN REVIEW PROCESS AND BE
 GREATLY APPRECIATED THANK YOU.
  
  
 2ND REVIEW COMMENTS:
  
 1. IN REFERENCE TO PREVIOUS COMMENT #5 PLEASE PROVIDE
 DETAILS SHOWING COMPLIANCE WITH TH E FBC ACC. SHOW ALL
 THE HEIGHTS OF GRAB BARS, TOILET SEATS, LAVATORY'S,
 MIRRORS, TOILET PAPER DISPENSERS, SHOWER CONTROL
 LOCATIONS AND SHOWER SEATS, DRINKING FOUNTAIN SHOW
 CLEAR FLOOR SPACE FOR ALL FIXTURES. PER WPB AMEND. TO
 FBC SEC. 107.2.1
  
 2. SHT. A2-52A SHOW INSIDE DIMENSIONS OF BATHROOMS
 207-205. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 3. BATHROOMS NEXT TO JACUZZI IN MENS AND WOMENS SPA
 SHALL BE ACCESSIBLE.PER FBC ACC. 213.2
  
 4. USING YOUR OCCUPANT TYPE AND LOAD FROM SHT. A0-32 I
 HAVE DETERMINED THAT ON THE 1ST LEVEL ( LOBBY) IT IS
 REQUIRED TO HAVE 4 WATER CLOSETS FOR THE MEN AND 4 FOR
 THE WOMEN 6 LAVS 2 DRINKING FOUNTAINS AND 1 SERVICE
 SINK . IT APPEARS THAT YOU ARE SHORT 3 WATER CLOSETS 5
 LAVS PER SEX AND 2 DRINKING FOUNTAIN AND 1 SERVICE
 SINK. PER FBC PL TABLE 403.1
  
 5. 4. USING YOUR OCCUPANT TYPE AND LOAD FROM SHT. A0-33
 I HAVE DETERMINED THAT ON THE 2ND LEVEL (AMENITY'S) IT
 IS REQUIRED TO HAVE 3 WATER CLOSETS FOR THE MEN AND 4
 FOR THE WOMEN 2 LAVS PER SEX 2 DRINKING FOUNTAINS AND 1
 SERVICE SINK . IT APPEARS THAT YOU ARE SHORT 1 WATER
 CLOSET-FOR THE WOMEN 2 DRINKING FOUNTAIN AND 1 SERVICE
 SINK. PER FBC PL TABLE 403.1
  
 6. PROVIDE A NOTE FOR BACKFLOW ON POOL FILL. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 7. PLEASE PROVIDE PLUMBING FLOOR PLAN-FOR LEVEL 1 AND
 2-3 ASININITY'S WITH GRID LINES 9-17 . PER WPB AMEND.
 TO FBC SEC. 107.2.1
  
 8. SHT. P5-28 THE HOT AND COLD WATER ISOMETRIC FOR SPA
 IS MISSING THE 2 SHOWERS IN WOMENS SPA. PER WPB AMEND.
 TO FBC SEC. 107.2.1
  
 9. SHT. P5-01+02 DOES NOT SHOW BRANCHES FOR AMENITY'S
 AND GUEST SUITES PLEASE CLARIFY. PER WPB AMEND. TO FBC
 SEC. 107.2.1
  
 10. SHT. P5-27 ISOMETRICS FOR UNITS 3,7,11 ARE MISSING
 THE WATER CLOSET AND LAVATORY'S. PER WPB AMEND. TO FBC
 SEC. 107.2.1
  
 11. SHT. P5-27 THE PIPE SIZING IS TO LITE TO BE EASILY
 READ PLEASE CHECK ALL SHEETS AND CORRECT. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 12. PLEASE PROVIDE HOT AND COLD WATER ISOMETRICS FOR
 UNITS ON LEVELS 18,19, PH 20,26 PER WPB AMEND. TO FBC
 SEC. 107.2.1
  
 13. SHT. P5-27 ISOMETRIC FOR UNIT A IS MISSING THE TUB
 IN THE BATHROOM AT GRID LINES S+6 ON SHT. P2-54C. PER
 WPB AMEND. TO FBC SEC. 107.2.1
  
 13 SHT P5-27 THE ISOMETRIC FOR UNIT B IS MISSING THE
 LAV IN THE BATHROOM AT GRID LINES P-8.5 ON SHT P2-54C.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 14. SHT.P5-27 THE BATHROOM ON GRID LINES P.5-6 ON SHT
 P2-54C IS SHOWN AS A SHOWER ON THE ISOMETRIC AND A TUB
 ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND. TO FBC
 SEC. 107.2.1
  
 15. SHT. P5-27 ISOMETRIC FOR UNIT C IS MISSING THE
 LAUNDRY SINK. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 16. SHT. P5-01 SHOW CONNECTION FOR TRASH SHOOT WASH
 RING ON RISER. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 17. SHT. P5-01 AT THE MECHANICAL LEVEL IT SHOWS THE 4IN
 AND 6IN CW CONNECTING TOGETHER CONNECTING TWICE PROVIDE
 A RISER THAT CLEARLY SHOWS WHERE PIPES CONNECT AND
 WHERE THEY CROSS. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 18. UNABLE TO LOCATE SANITARY RISER FROM LEVEL 16 DOWN.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 19. SHT P5-06 LABEL STACKS AND INDICATE ON THE DRAWING
 FLOOR LEVEL . PER WPB AMEND. TO FBC SEC. 107.2.1
  
 20. SHT P5-03-10 FIXTURE LAYOUT AND PIPE SIZING DO NOT
 MATCHISOMETRCS ON P5-10 THEYE UNCLEAR AND DON'T SEAM TO
 BE COMPLETE SOME OF THE BRANCHES SEAM TO CONNECT AT TWO
 DIFFERENT STACKS SOME STACKS DON'T CONNECT ANY WHERE.
 PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 21. PLEASE LABEL STORM RISERS ON THE ISOMETRIC DRAWINGS
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 22. P5-23 SHOWS 12IN LINE FROM POOL DECK DRAINS SHT
 P5-04 SHOWS 8IN CLARIFY. PER WPB AMEND. TO FBC SEC.
 107.2.1
  
 23. SHT- 23 DETAIL #2 I WAS UNABLE TO LOCATE THESE
 DRAINS ON FOR PLANS LABEL WITH LOCATION. PER WPB AMEND.
 TO FBC SEC. 107.2.1
  
 24. SHT P5-04 PROVIDE SQFT ON RISERS. PER WPB AMEND. TO
 FBC SEC. 107.2.1
  
 25. SHT. P5-21 INDICATE ON PLAN AT WHAT PITCH THE
 PIPING WILL BE INSTALLED AND-SHOW SQFT ON EACH SECTION
 OF PIPE. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 26. SHT. P5-21 THE ISOMETRIC FOR RD 11,19,20,21IT IS
 UNCLEAR HOW OR WHERE TO THE RISERS. PER WPB AMEND. TO
 FBC SEC. 107.2
  
 27. SHT. P-28 SHOWS 2 SINKS NEXT TO WASHING MACHINES I
 COULD NOT FIND THEM ON THE FLOOR PLAN. PER WPB AMEND.
 TO FBC SEC. 107.2.1
  
 28. P5-06 LABEL RISER AN AND INDICATE LOCATION ON FLOOR
 PLAN. PER WPB AMEND. TO FBC SEC. 107.2.1
  
 29. P5-07THRU21 ISOMETRICS ARE UNCLEAR WHERE PIPES
 CONNECT SOME PIPES DO NOT CONNECT . PROVIDE A CLEAR AND
 CONCISE DRAWING SHOWING ALL PIPE SIZING AND VENT STACKS
 VS SOIL STACKS , YOU MAY HAVE TO EXPAND THE ISOMETRICS
 LARGER SO BATHROOM GROUPS DON'T RUN TOGETHER AND APPEAR
 TO CONNECT. PER WPB AMEND. TO FBC SEC. 107.2.1
  
  
 IN YOUR RESPONSE LETTER MANY OF YOUR NARRATIVES JUST
 SAY REFER TO REVISED SHEET THIS DOES NOT GIVE ME MUCH
 INFORMATION. IF YOU COULD REFERENCE A SPECIFIC SHEET IT
 WOULD GREATLY EXPEDITE MY PLAN REVIEW PROCESS AND BE
 GREATLY APPRECIATED THANK YOU.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
  
  
  
  
 POOL COMMENTS:
  
 1. POOL ,HOT SPA POOL , HIS AND HER JACUZZIS AND ALL
 WATER FEATURES REQUIRE SEPARATE PERMIT FROM MAIN
 BUILDING.\
 2. SHALL OBTAIN OPERATING PERMIT FROM PALM BEACH COUNTY
 HEALTH DEPARTMENT. SHOW NOTE ON PLAN
 PER FBC SEC. 454
 NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS
 APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-9,
 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 514, FLORIDA
 STATUTES. THE REGULATION AND ENFORCEMENT OF THE INITIAL
 AND ANNUAL OPERATION PERMIT FOR PUBLIC POOLS ARE
 PREEMPTED TO THE DOH. THE CONSTRUCTION PERMIT HOLDER IS
 RESPONSIBLE FOR OBTAINING AN OPERATION PERMIT ISSUED BY
 DOH, AS A PUBLIC SWIMMING POOL SHALL NOT BE PUT INTO
 OPERATION WITHOUT AN INSPECTION AND OPERATION PERMIT
 ISSUED FROM THE DOH. DOH MAY GRANT VARIANCES FROM THE
 PROVISIONS OF THE FLORIDA BUILDING CODE SPECIFICALLY
 PERTAINING TO PUBLIC SWIMMING POOLS AND BATHING PLACES
 AS AUTHORIZED BY SECTION 514.0115, FLORIDA STATUTES.
 BUILDING OFFICIALS SHALL RECOGNIZE AND ENFORCE VARIANCE
 ORDERS ISSUED BY THE DEPARTMENT OF HEALTH PURSUANT TO
 SECTION 514.0115(5), FLORIDA STATUTES INCLUDING ANY
 CONDITIONS ATTACHED TO THE GRANTING OF THE VARIANCE.
  
  
 14. ONE URINAL IS REQUIRED IN MEN?S POOL BATHROOM. PER
 FBC PL TABLE 403.6 AND SEC 403.6 SHT. A2.52B DOES NOT
 SHOW URINAL IN MENS BATHROOM.
  
 18. SHOW COMPLIANCE FOR OZONE EQUIPMENT ROOM
 VENTILATION MUST COMPLY WITH FBC SEC. 545.1.6.5.16.4.5
 PLEASE PROVIDE SHT. NUMBERS
  
 24. PROVIDE MSDS SHEETS FOR ALL CHEMICALS USED. PER WPB
 AMEND. TO FBC 107.2.
  
 28. OZONE GENERATING EQUIPMENT ELECTRICAL COMPONENTS
 AND WIRING SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 27 OF THIS CODE AND THE MANUFACTURER SHALL
 PROVIDE A CERTIFICATE OF CONFORMANCE. THE PROCESS
 EQUIPMENT SHALL BE PROVIDED WITH AN EFFECTIVE MEANS TO
 ALERT THE USER WHEN A COMPONENT OF THIS EQUIPMENT IS
 NOT OPERATING PER FBC 454.1.6.5.16.4.1 SHOW NOTE ON
 PLAN
  
 29. PROVIDE SPECS FOR CHANNEL DRAINS FOR SPAL. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 NEW COMMENTS
  
 1. FOR THE TRANSFER WALL AT HOT SPA SHOW COMPLIANCE
 WITH FBC ACC (A) 1009.4.1 CLEAR DECK SPACE.
 A CLEAR DECK SPACE OF 60 INCHES (1525 MM) MINIMUM BY 60
 INCHES (1525 MM) MINIMUM WITH A SLOPE NOT STEEPER THAN
 1:48 SHALL BE PROVIDED AT THE BASE OF THE TRANSFER
 WALL. WHERE ONE GRAB BAR IS PROVIDED, THE CLEAR DECK
 SPACE SHALL BE CENTERED ON THE GRAB BAR. WHERE TWO GRAB
 BARS ARE PROVIDED, THE CLEAR DECK SPACE SHALL BE
 CENTERED ON THE CLEARANCE BETWEEN THE GRAB BARS.
 (B)1009.4.2 HEIGHT.
 THE HEIGHT OF THE TRANSFER WALL SHALL BE 16 INCHES (405
 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM MEASURED
 FROM THE DECK.
 (C)1009.4.5 GRAB BARS.
 AT LEAST ONE GRAB BAR COMPLYING WITH 609 SHALL BE
 PROVIDED ON THE TRANSFER WALL. GRAB BARS SHALL BE
 PERPENDICULAR TO THE POOL WALL AND SHALL EXTEND THE
 FULL DEPTH OF THE TRANSFER WALL. THE TOP OF THE
 GRIPPING SURFACE SHALL BE 4 INCHES (100 MM) MINIMUM AND
 6 INCHES (150 MM) MAXIMUM ABOVE TRANSFER WALLS. WHERE
 ONE GRAB BAR IS PROVIDED, CLEARANCE SHALL BE 24 INCHES
 (610 MM) MINIMUM ON BOTH SIDES OF THE GRAB BAR. WHERE
 TWO GRAB BARS ARE PROVIDED, CLEARANCE BETWEEN GRAB BARS
 SHALL BE 24 INCHES (610 MM) MINIMUM.
  
 2. DETAILS NOT SHOWN FOR BACKFLOW /AIR GAP ON FILL
 LINES AND OVER FLOW FILL LINE BOX FOR WATER FEATURE.
 PER WPB AMEND TO FBC 107.2.1
  
 3. THE CRYSTAL FOUNTAIN SHOWS AN OVERFLOW CONNECTING TO
 A SEWER YOU SHALL RECEIVE APPROVAL FROM ENGINEERING
 DEPARTMENT TO CONNECT ANY OVERFLOW FROM WATER FEATURES
 OR POOL EQUIPMENT CONTACT MANUEL GONZALEZ 561-494-1085
  
  
  
  
  
  
  
 DO TO THE DEFICIENCY'S AND SOME SHEETS BEING UNCLEAR A
 COMPLETE AND COMPREHENSIVE REVIEW OF THE PLUMBING
 SYSTEMS CAN NOT BE COMPLETED AT THIS TIME. THIS MAY
 GENERATE MORE COMMENTS UPON SECOND REVIEW.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  