Text |
| 2016-08-17 10:38:40 | |
| | |
| | 2ND REVIEW: FBC 2010 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | GAS COMMENTS: 1ST REVIEW HAVE NOT COMPLIED |
| | |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS FOR 2PSI |
| | AND .5PSI SYSTEMS PER FBC-2010 FUEL GAS, SECS. 402.4.1, |
| | 402.4.2. |
| | |
| | |
| | |
| | |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). |
| | |
| | |
| | |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR EACH |
| | APPLIANCE WITH CUBIC FT. REQUIRED AND WHAT IS PROVIDED |
| | PER THE FBC-2010 FUEL GAS CODE SEC. 304. |
| | |
| | |
| | |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE |
| | SEC. 502 THRU 505. |
| | |
| | 2ND REVIEW: |
| | |
| | 1. IN THE NOTE FOR GAS CALCULATIONS YOU LISTED TABLE |
| | 402.4(6) IN THE FBC FUEL GAS THIS TABLE IS FOR COPPER |
| | TUBING THE PLAN SHOWS SCHEDULE 40 METALLIC PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | 2. NOTE #1 PLEASE CLARIFY WHAT TYPE OF PIPING IS GOING |
| | TO BE USED UNDERGROUND. METALLIC PIPING IS EXTREMELY |
| | RESTRICTIVE ON USE UNDERGROUND. PER WPB AMEND TO FBC |
| | 107.2.1 FBC FUEL GAS 404.9 |
| | 3. SHOW REGULATORS AND DRIP LEGS.1. IN THE NOTE FOR GAS |
| | CALCULATIONS YOU LISTED TABLE 402.4(6) IN THE FBC FUEL |
| | GAS THIS TABLE IS FOR COPPER TUBING THE PLAN SHOWS |
| | SCHEDULE 40 METALLIC PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | |
| | 4. BRANCH SIZE FOR TYPICAL UNIT ON GAS RISER 4 SHOWS |
| | 3/4 THE REST OF THE RISERS SHOW 1/2 PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | 5. NOTE #4 PROVIDE ISOMETRIC AND FLOOR PLAN DRAWING |
| | SHOWING THE VENT LOCATIONS OF THE PRESSURE REGULATORS. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | 6. SHOW GAS LINE ON A FLOOR PLAN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | |
| | |